P/N 42-9472 Copyright 2008 Mestek, Inc.
Cast iron condensing boiler
Cast iron condensing boiler
— Control manual
Level 1
next
item
to select
Level 2
next item
to select
back one level
Level 3
next item
to select
back one level
Level 4
next item
to select
back one level
Default {Range}
to change value
to accept value and return to
previous menu level
Typical line
(Display shows two
lines at a time; cursor
indicates active line)
200i V X.X
Shows fi rmware version number
200i V 1.0
BOILERS
# BOILERS
1 {1 to 16} — display only
# BOILERS
1
LEAD BOILER
1 — display only — the lead boiler is the boiler with
a HEADER sensor connected
LEAD BOILER
1
HEAT BAND
30 °F {10 to 50°F}
HEAT BAND
30°F
HEAT NET BOILERS
123456789ABCDEFG
Display only — shows 1 through the number of
boilers on the network
HEAT NET BOILERS
123456
SETPOINTS
LOC SETPT
180°F {140 to 180°F}
LOC SETPT
180°F
SOURCE
AUTO {AUTO, 4-20MA}
SOURCE AUTO
DHW SETPT
180°F {140 to 180°F}
DHW SETPT
180°F
OP LIMIT
205°F {145 to 205°F}
OP LIMIT
215°F
LIMIT BAND
10°F {1 to 50°F}
LIMIT BAND
20°F
INDOOR AIR
IA RESET
OFF {ON or OFF}
IA RESET
OFF
AVG TIME
60 MIN {30 to 120 minutes}
AVG TIME
60MIN
SET IAR SETPTS
DELTA TEMP
@ HI IAR%
10°F {10 to 20°F}
70% {40 to 70%}
DELTA TEMP
10°F
@ HI IAR%
70%
DELTA TEMP
@ LO IAR%
20°F {10 to 20°F}
40% {40 to 70%}
DELTA TEMP
20°F
@ LO IAR%
40%
VIEW IAR VALUES
Display only, not changeable here — shows values
for 8 zones
70 70 70 70
70 70 70 70
OUTDOOR AIR
OA SHUTDOWN
OFF {ON or OFF}
OA SHUTDOWN OFF
OA SETPT
68°F {40 to 100°F}
OA SETPT
68°F
OA RESET
OFF {ON or OFF}
OA RESET
OFF
SET OA SETPTS
LOW WATER
@ HI OA
140°F {60 to 150°F}
70°F {50 to 90°F}
LOW WATER
140°F
@ HI OA
70°F
HI WATER
@ LOW OA
180°F {70 to 180°F}
10°F {-35 to +40°F}
HI WATER
180°F
@ LOW OA
10°F
PUMP OPTIONS
DELTA ENAB
OFF {ON or OFF}
DELTA ENAB
OFF
DELTA TEMP
10°F {10 to 50°F}
DELTA TEMP
10°F
PURGE TIME
0 seconds {0 to 255 seconds}
PURGE TIME
120s
ALWAYS ON
NO {YES or NO}
ALWAYS ON
NO
MASTER PUMP
OFF {ON or OFF}
MASTER PUMP OFF
NIGHT SETBACK
SETBACK # X
1 {1 through 4}
SETBACK #
2
ENTRY IS OFF
SETBACK
20°F {0 to 50°F}
ENTRY IS
OFF
ST DAY
SUN {SUN, MON, TUE, WED, THU, FRI, SAT}
ST DAY
THU
ST TIME
12:00AM
ST TIME
3:00PM
ENDDAY
SUN {SUN, MON, TUE, WED, THU, FRI, SAT}
ENDAY SAT
ENDTIME
12:00AM
ENDTIME 10:00PM
OPTIONS
TEMP SCALE
°F {°F or °C}
TEMP SCALE
°F
KEY CLICK
ON {ON or OFF}
KEY CLICK
ON
SKIP PASSW
ON {ON or OFF}
SKIP PASSW
ON
BRIGHTNESS
50% {12, 25, 37, 50, 62, 75, 87, 100%}
BRIGHTNESS 50%
Table 7
Setup menus (
see Table 8, page 25 for explanations
)
To enter Setup: From STANDBY, hold
for 5 seconds. Then press
with cursor on SETUP. Make sure there is no call for heat at
the boiler before attempting to perform setup adjustments.
To return to STANDBY, press/release
until the display returns to standby, or turn boiler ON/OFF switch off , then on.
Control menus and adjustments
(continued)
4