background image

13

P/N 42-9472 Copyright 2008 Mestek, Inc.

Cast iron condensing boiler

 

Cast iron condensing boiler

 — Control manual

Figure 10

 

RS485 communications board

Turn on power to the master boiler and set its on/off  switch to ON.
You should hear at least 2 beeps.
Th e control’s fi rmware version number will display.

 Aft er the control’s timer fi nishes, the display will 

 

show STANDBY and SYS SET. Th

 is verifi es that 

 

the master boiler is setup correctly as the master. 

Th e same display will show on member boilers when there is a call for heat from 
the master boiler. When there is no call for heat at a member boiler, the display will 
show LOC SET instead.
If the master is functioning correctly, the yellow LED’s on the H-Link jack ports 
will blink. Th e blinking indicates that the master is trying to communicate with 
member boilers.
If a FAULT message is displayed, clear the faults until the STANDBY message is 
displayed. Refer to troubleshooting suggestions at the end of this manual if you 
cannot resolve the issue.

Member boiler cables

Begin with the fi rst member boiler.
Plug the other end of the master boiler’s communications cable to the member boiler’s 
input port (Figure 10, page 13, item 2 for RJ45 cable or item 4 for 3-wire cable).
Connect cables to all of the member boilers by cabling from one to the next. Connect 
incoming cables to item 1 or 4, Figure 10, page 13. Connect outgoing cables to item 
2 or 4. (Note that shielded cable wires will share terminals when using item 4.)

Check the network

Turn the power on and the on/off  switch to ON for all of the member boilers.
Allow time for each boiler to initialize.
Aft er about 30 seconds, the master boiler should recognize the member boilers.

 Navigate to the BOILERS menu, then to HEAT 

 

NET BOILERS display. Th e master control will 

 

show the boilers it recognizes. Values from 10 to 

15 will display as lett ers (10=A, 11=B, 12=C, 13=D, 14=E and 15=F).
If the display shows a blank space, such as “123_56789ABC,” the control does not 
detect the missing boiler (boiler 4). Check the yellow LED on the communication 
port of the missing boiler.
NORMAL connection — LED should fl ash steadily, about twice per second.
TERMINATION incorrect — LED will fl ash rapidly and stay on.
OPEN connection — LED does not fl ash at all.
If a FAULT message is displayed, clear the faults until the STANDBY message is 
displayed. Refer to troubleshooting suggestions at the end of this manual if you 
cannot resolve the issue.

Start the system

Turn off  power to all boilers.
Connect all call for heat wiring to the boilers.
Turn on power to all boilers and turn the on/off  switches to ON.
Th e boilers should now operate normally, as described in the Boiler manual.
Th e master boiler will sequence and modulate boilers as necessary to control the 
water temperature.
Th e master boiler will show the number of boilers fi ring as well as the temperature 
and heat band display. Use the UP/DOWN keys to scroll through the displays to 
watch the process of starting and stopping boilers.

2.
3.
4.
5.

6.

7.

1.
2.

3.

1.
2.
3.
4.

5.

6.
7.
8.
9.

1.
2.
3.
4.
5.

6.

RJ45 SmartCycle cable IN from master or previous 
member
RJ45 SmartCycle cable OUT to next member boiler
Shielded wire (3-2ire), option to RJ45 cable, Smart-
Cycle communications INPUT and connection for 
additional boilers on the network
Shielded wire (option to RJ45 cable) Modbus INPUT 
from building management system
USB cable port (for USB cable connection to a PC — 
required when updating control fi rmware)
RJ45 cable from building management system, when 
used
Plug for insertion into 200i control electrical connec-
tion panel (see page 3)
NOT SHOWN — An optional plug-in bridge is re-
quired to interface with building management systems 
that use BACnet or LonWorks protocol. Th e 200i 
control supports Modbus protocol with no additional 
components except the RS485 interface board.

1.

2.
3.

4.

5.

6.

7.

8.

Method 1:  SmartCycle modulation – local control 

(cont.)

1

Содержание 200i

Страница 1: ...ed with a dust freeairsupply Followtheinstructionmanualprocedurestoductairtotheboilerairintake Iftheboilerhasbeencontaminatedbyoperation with contaminated air follow the instruction manual guidelines...

Страница 2: ...nput from an external controller The control method used by the SmartCycle control is based on digital communications which elimi nates the need for analog control signals Analog signalinputs are supp...

Страница 3: ...ernal high limit and or low water cutoff if desired To flow switch when used Used to activate combustion air damper if desired To combustion air damper proving switch required when controlling combust...

Страница 4: ...4 P N 42 9472 Copyright 2008 Mestek Inc Cast iron condensing boiler Cast iron condensing boiler Control manual The Mestek 200iboiler with SmartCycleTM control...

Страница 5: ...Each boiler requires the RS485 interface board and cable Boiler setup is essentially the same as for method 1 with the exception that each boiler must be assigned both a SmartCycle network address and...

Страница 6: ...inFigure2 Install a fused service switch mounted and installed in accordance with all appli cable codes 1 2 3 4 5 6 7 8 9 10 1 1 2 3 Figure 1 Electrical connection board see item 10 page 3 for locatio...

Страница 7: ...potential damage from heat pocket ing in the top of the heat exchanger Thepostpurgecirculatorisfactory pipedandpre wired Do not change the usage the wiring the location or the piping Boiler circulato...

Страница 8: ...ard If there is more than one transformer provide one wire from each transformer common side to one of the IAR negative terminals IAR Sensor wiring Header sensor is required A header sensor must be in...

Страница 9: ...8 Mestek Inc Cast iron condensing boiler Cast iron condensing boiler Control manual Figure 7 200i wiring summary wiring to electrical connection board Method 1 SmartCycle modulation local control cont...

Страница 10: ...sing boiler Cast iron condensing boiler Control manual Figure 8 200i wiring summary wiring to electrical connection board continued see Figure 7 page 9 for terminal strip locations Also see Figure 5 p...

Страница 11: ...trol system water temperature if member boilers were to input heat to the system without control from the master DHW operation in particular would raise the supply temperature from overriding boilers...

Страница 12: ...s Carefully read the parameter explanations in Table 8 page 25 through page 29 When adjusting the limit band operating limit OP LIMIT local setpoint LOC SETPOINT and DHW setpoint make sure the operati...

Страница 13: ...C 13 D 14 E and 15 F If the display shows a blank space such as 123_56789ABC the control does not detectthemissingboiler boiler4 ChecktheyellowLEDonthecommunication port of the missing boiler NORMAL c...

Страница 14: ...r 15 MainValve 31 Present Boiler Detected Overview This method uses an RS485 digital communications cable with the Modbus protocol to control a boiler or SmartCycle network Theboilerorboilernetworkwil...

Страница 15: ...of seconds that the boiler has been running For instance Register 29 65536 Register 30 Boiler 1 runtime in seconds Boiler 1 is the master boiler Boilers 2 16 are member boilers 0 4294967295 seconds BA...

Страница 16: ...connection as shown in Fig ure 12 Install a fused service switch mounted and installed in accordance with all appli cable codes 1 2 3 4 5 6 7 8 9 1 1 2 3 Figure 11 Electrical connection board see item...

Страница 17: ...ntial damage from heat pocketing in the top of the heat exchanger Thepostpurgecirculatorisfactory pipedandpre wired Do not change the usage the wiring the location or the piping Boiler circulator See...

Страница 18: ...ach boiler requires a return water temperature sensor DHW wiring ONLY if using DHW override mode The boiler or boilers must be piped with isolation valves and wired for override operation Override of...

Страница 19: ...72 Copyright 2008 Mestek Inc Cast iron condensing boiler Cast iron condensing boiler Control manual Method 3 External 4 20ma control continued 3 Figure 16 200i wiring summary wiring to electrical conn...

Страница 20: ...ast iron condensing boiler Cast iron condensing boiler Control manual Method 3 External 4 20ma control continued 3 Figure 17 200i wiring summary wiring to electrical connection board continued see Fig...

Страница 21: ...erminals This will prevent the boiler for attempting to cycle during the setup process See Control menus and adjustments beginning on page 22 for a complete list of control parameters and explanations...

Страница 22: ...e of the display as shown providing information on various setpoints and parameters The display LOC SET means the setpoint temperature Figure 18 shows the fac tory default values Accessing setup menus...

Страница 23: ...P 20 F LO IAR 40 VIEW IARVALUES Display only not changeable here shows values for 8 zones 70 70 70 70 70 70 70 70 OUTDOOR AIR OA SHUTDOWN OFF ON or OFF OA SHUTDOWN OFF OA SETPT 68 F 40 to 100 F OA SET...

Страница 24: ...inutes 0 to 15 minutes 2 MINUTES 0 SECONDS MOD DELAYTIME 10 seconds 0 to 60 minutes 0 MINUTES 10 SECONDS MOD MAX LAST 50 25 to 100 STOP MOD MAX 50 STOP BAND OFSET 5 F 0 to 50 F EARLY STOP 5 BLR STARTT...

Страница 25: ...r temperature when the DHW Demand terminals see a closed contact DHW tank temperature control calls for heat for example OP LIMIT SETPOINTS This is the temperature at the boiler outlet or header senso...

Страница 26: ...ly water temperature High water at low outside air means the design water temperature for maximum load at ODT or outside design temperature for the installation The other end of the reset curve is the...

Страница 27: ...ivate its end switch SYSTEM CLOCK Set the system clock time day of week month day and year on start up and after any power outage to ensure the data log time stamp information will be accurate LOCAL A...

Страница 28: ...should generally be left at factory default BAND ADVANCED SETUP MODULATION PID This parameter should generally be left at factory default ROTATION ADVANCED SETUP FIRING MODE Select the rotation method...

Страница 29: ...ogram will start and show an option screen Select Install USB Drivers to install the program onto the computer After the USB driver installation is complete select Install Firmware Update Plug a USB c...

Страница 30: ...rrow keys to scroll through the log entries entry number and date are on the first line of the log screen Each log entry includes three screens as described below The top line remains the same in all...

Страница 31: ...ntactors or other devices connected to it If all grounding is correct there may be an issue with radiated or induced electrical noise interference Thismaybecausedbyarcingacrossacontactor scontactswhen...

Страница 32: ...TER boiler to act as a MASTER the header sensor must be set to TYPEZ and there must be a header sensor present At power up the header sensor is auto detected If the temperature of the header sensor at...

Отзывы: