background image

18

P/N 42-9472 Copyright 2008 Mestek, Inc.

Cast iron condensing boiler

 

Cast iron condensing boiler

 — Control manual

Method 3:  External 4-20ma control 

(continued)

3

4-20mA operation

A 4.02 mA current signal will start the boiler, at low fi re. A 
20mA signal will cause the boiler to go to full input.

Between these input signal limits, the boiler modulates. Th

 e 

boiler fi ring rate percentage is equal to the percentage of the 
signal between 0 and 20 mA. Example, a signal of 12 mA is 
60% of 20 mA, so the boiler fi ring rate would be 60% of max.

In addition to the 4-20mA signal, the remote controller 
must also close a contact across each boiler’s Remote En-
able contact in order for the boiler to fi re.

See Figure 16, page 19 for wiring. Notice that the boiler 4-
20mA terminals are wired in series.

IAR (Indoor Air Reset) wiring — 
apply ONLY if using space heating 
override mode

IAR can only be used if one or more of the boilers is wired 
and piped for override operation. Override would occur 
when a contact closed across the Heat Demand terminals. 
While this contact is closed, the boiler will operate based on 
local control, including feedback for IAR if wired.

If override operation will be used, and you want to operate 
with IAR when in override mode, follow the instructions 
under Method 1 in this manual to wire for IAR. 

Sensor wiring

Header sensor cannot be used when the boilers 
are confi gured for remote operation by a 24-mA 
source.

Outdoor reset application can be done only in over-
ride mode

 — To operate with outdoor reset, purchase and 

install an outdoor sensor. Mount the sensor such that it is 
shielded from direct sunlight if possible and not likely to be 
covered by snow drift s or debris. Connect the outdoor sen-
sor leads to the master boiler’s electrical connection board 
as shown in Figure 8, page 10. (Member boilers could have 
their own outdoor sensor if they will be operated in over-
ride mode by closing the Heat Demand terminals.)

Return water temperature sensor

 — Th e return wa-

ter temperature sensor is optional, only needed if you want 
to automatically control the boiler postpurge pump cycle 
time. Install the sensor in a well in the boiler return piping. 
Connect the sensor leads to the electrical connection board 
as shown in Figure 8, page 10. Each boiler requires a return 
water temperature sensor.

DHW wiring — ONLY if using DHW 
override mode

The boiler (or boilers) must be piped with isolation 
valves and wired for override operation

. Override of 

the 4-20mA input will occur if a contact closes across the 
boiler’s DHW Demand terminals.

1.

2.

3.

4.

To operate the boiler for domestic water heating with a 
storage tank, install and pipe the tank according to the tank 
manufacturer’s instructions and the recommended piping 
diagrams in this manual. Consult the factory for applica-
tions not covered.

Th e circulator used for DHW must be operated by a circula-
tor relay or zone controller that is activated when the tank 
aquastat calls for heat.

Connect the tank aquastat terminals across the DHW 
DEMAND terminals on the master boiler’s electrical con-
nection board as shown in Figure 7, page 9. (Member 
boilers could be connected to tank aquastats if they are 
piped appropriately and intended to operate in override 
mode.)External interlocks

Wire external limits and fl ow switch, when used, as shown 
in Figure 17, page 20.

Th e combustion air interlocks cannot be used when operat-
ing with a 24-mA remote control. Combustion air damper 
control must be done by the remote control system.

Overrides — Control priorities

Th e 200i control can provide override operation for any or 
all member boilers. Th is requires the boilers be piped with 
appropriate isolation piping and controls.

Override is done by closing a contact across the Heat De-
mand or DHW Demand terminals of any boiler. Th ese 
priority inputs override all 4-20mA input controls to the 
boiler.

DHW Demand

 — Th e DHW Demand closure takes prior-

ity for ALL boilers, including the master and all members. 
When DHW Demand closes, the boiler or boilers immedi-
ately switch to DHW operation, including sett ing the water 
temperature to the DHW Setpoint.

Space heating, Heat Demand 

— If any member boiler 

sees closure across its Heat Demand terminals it will begin 
operation in space heating mode independently of com-
mands from the 4-20mA input source.

  Do not wire boilers for override operation unless 

the piping design provides automatic isolation of 
the overriding boilers.

  Override operation control setup — Boilers 

must be set up with operating parameters 
necessary during their override operation; i.e., 
local setpoint, DHW setpoint, etc.

Summary — priority sequence is:

Priority 1 = DHW Demand

Priority 2 = Heat Demand

Priority 3 = 4-20mA Input/Enable

5.

6.

1.

2.

3.

4.

5.

Содержание 200i

Страница 1: ...ed with a dust freeairsupply Followtheinstructionmanualprocedurestoductairtotheboilerairintake Iftheboilerhasbeencontaminatedbyoperation with contaminated air follow the instruction manual guidelines...

Страница 2: ...nput from an external controller The control method used by the SmartCycle control is based on digital communications which elimi nates the need for analog control signals Analog signalinputs are supp...

Страница 3: ...ernal high limit and or low water cutoff if desired To flow switch when used Used to activate combustion air damper if desired To combustion air damper proving switch required when controlling combust...

Страница 4: ...4 P N 42 9472 Copyright 2008 Mestek Inc Cast iron condensing boiler Cast iron condensing boiler Control manual The Mestek 200iboiler with SmartCycleTM control...

Страница 5: ...Each boiler requires the RS485 interface board and cable Boiler setup is essentially the same as for method 1 with the exception that each boiler must be assigned both a SmartCycle network address and...

Страница 6: ...inFigure2 Install a fused service switch mounted and installed in accordance with all appli cable codes 1 2 3 4 5 6 7 8 9 10 1 1 2 3 Figure 1 Electrical connection board see item 10 page 3 for locatio...

Страница 7: ...potential damage from heat pocket ing in the top of the heat exchanger Thepostpurgecirculatorisfactory pipedandpre wired Do not change the usage the wiring the location or the piping Boiler circulato...

Страница 8: ...ard If there is more than one transformer provide one wire from each transformer common side to one of the IAR negative terminals IAR Sensor wiring Header sensor is required A header sensor must be in...

Страница 9: ...8 Mestek Inc Cast iron condensing boiler Cast iron condensing boiler Control manual Figure 7 200i wiring summary wiring to electrical connection board Method 1 SmartCycle modulation local control cont...

Страница 10: ...sing boiler Cast iron condensing boiler Control manual Figure 8 200i wiring summary wiring to electrical connection board continued see Figure 7 page 9 for terminal strip locations Also see Figure 5 p...

Страница 11: ...trol system water temperature if member boilers were to input heat to the system without control from the master DHW operation in particular would raise the supply temperature from overriding boilers...

Страница 12: ...s Carefully read the parameter explanations in Table 8 page 25 through page 29 When adjusting the limit band operating limit OP LIMIT local setpoint LOC SETPOINT and DHW setpoint make sure the operati...

Страница 13: ...C 13 D 14 E and 15 F If the display shows a blank space such as 123_56789ABC the control does not detectthemissingboiler boiler4 ChecktheyellowLEDonthecommunication port of the missing boiler NORMAL c...

Страница 14: ...r 15 MainValve 31 Present Boiler Detected Overview This method uses an RS485 digital communications cable with the Modbus protocol to control a boiler or SmartCycle network Theboilerorboilernetworkwil...

Страница 15: ...of seconds that the boiler has been running For instance Register 29 65536 Register 30 Boiler 1 runtime in seconds Boiler 1 is the master boiler Boilers 2 16 are member boilers 0 4294967295 seconds BA...

Страница 16: ...connection as shown in Fig ure 12 Install a fused service switch mounted and installed in accordance with all appli cable codes 1 2 3 4 5 6 7 8 9 1 1 2 3 Figure 11 Electrical connection board see item...

Страница 17: ...ntial damage from heat pocketing in the top of the heat exchanger Thepostpurgecirculatorisfactory pipedandpre wired Do not change the usage the wiring the location or the piping Boiler circulator See...

Страница 18: ...ach boiler requires a return water temperature sensor DHW wiring ONLY if using DHW override mode The boiler or boilers must be piped with isolation valves and wired for override operation Override of...

Страница 19: ...72 Copyright 2008 Mestek Inc Cast iron condensing boiler Cast iron condensing boiler Control manual Method 3 External 4 20ma control continued 3 Figure 16 200i wiring summary wiring to electrical conn...

Страница 20: ...ast iron condensing boiler Cast iron condensing boiler Control manual Method 3 External 4 20ma control continued 3 Figure 17 200i wiring summary wiring to electrical connection board continued see Fig...

Страница 21: ...erminals This will prevent the boiler for attempting to cycle during the setup process See Control menus and adjustments beginning on page 22 for a complete list of control parameters and explanations...

Страница 22: ...e of the display as shown providing information on various setpoints and parameters The display LOC SET means the setpoint temperature Figure 18 shows the fac tory default values Accessing setup menus...

Страница 23: ...P 20 F LO IAR 40 VIEW IARVALUES Display only not changeable here shows values for 8 zones 70 70 70 70 70 70 70 70 OUTDOOR AIR OA SHUTDOWN OFF ON or OFF OA SHUTDOWN OFF OA SETPT 68 F 40 to 100 F OA SET...

Страница 24: ...inutes 0 to 15 minutes 2 MINUTES 0 SECONDS MOD DELAYTIME 10 seconds 0 to 60 minutes 0 MINUTES 10 SECONDS MOD MAX LAST 50 25 to 100 STOP MOD MAX 50 STOP BAND OFSET 5 F 0 to 50 F EARLY STOP 5 BLR STARTT...

Страница 25: ...r temperature when the DHW Demand terminals see a closed contact DHW tank temperature control calls for heat for example OP LIMIT SETPOINTS This is the temperature at the boiler outlet or header senso...

Страница 26: ...ly water temperature High water at low outside air means the design water temperature for maximum load at ODT or outside design temperature for the installation The other end of the reset curve is the...

Страница 27: ...ivate its end switch SYSTEM CLOCK Set the system clock time day of week month day and year on start up and after any power outage to ensure the data log time stamp information will be accurate LOCAL A...

Страница 28: ...should generally be left at factory default BAND ADVANCED SETUP MODULATION PID This parameter should generally be left at factory default ROTATION ADVANCED SETUP FIRING MODE Select the rotation method...

Страница 29: ...ogram will start and show an option screen Select Install USB Drivers to install the program onto the computer After the USB driver installation is complete select Install Firmware Update Plug a USB c...

Страница 30: ...rrow keys to scroll through the log entries entry number and date are on the first line of the log screen Each log entry includes three screens as described below The top line remains the same in all...

Страница 31: ...ntactors or other devices connected to it If all grounding is correct there may be an issue with radiated or induced electrical noise interference Thismaybecausedbyarcingacrossacontactor scontactswhen...

Страница 32: ...TER boiler to act as a MASTER the header sensor must be set to TYPEZ and there must be a header sensor present At power up the header sensor is auto detected If the temperature of the header sensor at...

Отзывы: