12

P/N 42-9472 Copyright 2008 Mestek, Inc.

Cast iron condensing boiler

 

Cast iron condensing boiler

 — Control manual

Table 2

 Control 

parameters

Parameter

Master

boiler

Member

boiler

(see notes)

HEAT BAND

Set on master boiler only

LOC SETPOI NT

Set

HD only

1

SOURCE

Set

HD or DHW only

1,2

DHW SETPOINT

Set if DHW will 

be used

DHW only

2

OP LIMIT

Set

Set

LIMIT BAND

Set

Set

IA RESET

ON if IAR is used, 

or set to OFF

Do not set

OA SHUTDOWN

Set ON if used

or set to OFF

HDOA only

3

OA SETPOINT

Set if used

HDOA only

3

OA RESET

Set if used

HDOA only

3

OA SETPTS

Set if used

HDOA only

3

DELTA ENABLE

Set if used

Set if used

DELTA TEMP

Set if used

Set if used

PURGE TIME

Set if used

Set if used

ALWAYS ON

Set if used

Set if used

MASTER PUMP

Set if used

Do not set

NIGHT SETBACK

Set on master boiler only

OPTIONS (all)

Set

Set

AUX FUNCTIONS

Set on master boiler only

SYSTEM CLOCK

Set

Set

LOCAL ADD

Automatic

Set (beginning at 2)

CONSOLE ADD

Automatic

Set (beginning at 2)

MODULAR BOILER

Set on master boiler only

MODULATION PID

Set on master boiler only

FIRING MODE

Set on master boiler only

SENSOR #

Set

HD/HDOA only

1,3

TYPE

Set

HD/HDOA only

1,3

CALIBRATE ?

On any boiler if required

PASSWORD

Set

Set

COMMUNICATIONS

Set

Set

LOAD DEFAULTS

On any boiler if required

SYSTEM

On any boiler if required

Notes:

1 — HD Only

 means to set the parameter for a member boiler only if it is wired for 

Heat Demand override.

2 — DHW Only

 means to set the parameter for a member boiler only if it is wired 

for DHW Demand override.

3 — HDOA Only

 means to set these parameters only if the member boiler will be 

operated with outdoor reset when put in override mode with closure across its Heat 
Demand terminals (requires outdoor sensor connected to boiler).

Set control parameters on keypads

  Before turning boilers on to set parameters, disconnect all call for heat 

wiring at the electrical connection boards. Th is will prevent the boiler 
for att empting to cycle during the setup process.

See “Control menus and adjustments,” beginning on page 22 for a complete list of 
control parameters and explanations.
Carefully read the parameter explanations in Table 8, page 25 through page 29.
When adjusting the limit band, operating limit (OP LIMIT), local setpoint (LOC 
SETPOINT) and DHW setpoint, make sure the operating temperature bands do 
not overlap or cause potential for nuisance cycling.
Indoor air reset — Use this option whenever possible. Th e indoor air technology 
monitors space heating demand to help the boiler operate at the highest possible 
effi  ciency throughout the season. To operate with IAR, you must wire to the IAR 
input terminals as described on page 18.
System clock — Set the system clock on all boilers to ensure the time stamps will 
be accurate in the data logs.
Turn on the power to each boiler and set the on/off  switch to ON as you set its 
parameters.
Use the boiler’s keypad to enter the parameters as described on page 22.
Aft er sett ing a boiler’s parameters, turn the power off  to the boiler until you are 
ready to start the boiler up following the Boiler manual instructions.
Set the master boiler and each member boiler, following the guidelines given in 
Table 2.

Start up boilers per 200i Boiler manual

Turn off  power to all boilers.
Follow all instructions in the 200i Boiler manual to start up each boiler and verify 
operation.

Connect network cables

 

Electrical shock hazard — 

Turn off  power to each boiler before 

att empting to connect the network cables.

  Before turning boilers on to check network operation, disconnect all 

call for heat wiring at the electrical connection boards. Th is will prevent 
the boiler for att empting to cycle during the setup process.

Master boiler cable

Connect an RJ45 cable to the master boiler H-Link OUT block (item 2, Figure 10, 
page 13) or 3-wire shielded cable to the H-Link terminal strip (item 4, Figure 10, 
page 13). Th e other end of this cable will be att ached to the fi rst member boiler in 
following steps.

1.

2.
3.

4.

5.

6.

7.
8.

9.

1.
2.

1.

 

Close the external manual gas valve on every boiler

 before 

proceeding. DO NOT open any gas valve, or att empt to fi re any 
boiler, until the boilers have been set up and verifi ed following 
the instructions in the 200i Boiler manual.

 

Failure to comply could cause a boiler failure, leading to possible 
severe personal injury, death or substantial property damage.

Method 1:  SmartCycle modulation – local control 

(cont.)

1

Содержание 200i

Страница 1: ...ed with a dust freeairsupply Followtheinstructionmanualprocedurestoductairtotheboilerairintake Iftheboilerhasbeencontaminatedbyoperation with contaminated air follow the instruction manual guidelines...

Страница 2: ...nput from an external controller The control method used by the SmartCycle control is based on digital communications which elimi nates the need for analog control signals Analog signalinputs are supp...

Страница 3: ...ernal high limit and or low water cutoff if desired To flow switch when used Used to activate combustion air damper if desired To combustion air damper proving switch required when controlling combust...

Страница 4: ...4 P N 42 9472 Copyright 2008 Mestek Inc Cast iron condensing boiler Cast iron condensing boiler Control manual The Mestek 200iboiler with SmartCycleTM control...

Страница 5: ...Each boiler requires the RS485 interface board and cable Boiler setup is essentially the same as for method 1 with the exception that each boiler must be assigned both a SmartCycle network address and...

Страница 6: ...inFigure2 Install a fused service switch mounted and installed in accordance with all appli cable codes 1 2 3 4 5 6 7 8 9 10 1 1 2 3 Figure 1 Electrical connection board see item 10 page 3 for locatio...

Страница 7: ...potential damage from heat pocket ing in the top of the heat exchanger Thepostpurgecirculatorisfactory pipedandpre wired Do not change the usage the wiring the location or the piping Boiler circulato...

Страница 8: ...ard If there is more than one transformer provide one wire from each transformer common side to one of the IAR negative terminals IAR Sensor wiring Header sensor is required A header sensor must be in...

Страница 9: ...8 Mestek Inc Cast iron condensing boiler Cast iron condensing boiler Control manual Figure 7 200i wiring summary wiring to electrical connection board Method 1 SmartCycle modulation local control cont...

Страница 10: ...sing boiler Cast iron condensing boiler Control manual Figure 8 200i wiring summary wiring to electrical connection board continued see Figure 7 page 9 for terminal strip locations Also see Figure 5 p...

Страница 11: ...trol system water temperature if member boilers were to input heat to the system without control from the master DHW operation in particular would raise the supply temperature from overriding boilers...

Страница 12: ...s Carefully read the parameter explanations in Table 8 page 25 through page 29 When adjusting the limit band operating limit OP LIMIT local setpoint LOC SETPOINT and DHW setpoint make sure the operati...

Страница 13: ...C 13 D 14 E and 15 F If the display shows a blank space such as 123_56789ABC the control does not detectthemissingboiler boiler4 ChecktheyellowLEDonthecommunication port of the missing boiler NORMAL c...

Страница 14: ...r 15 MainValve 31 Present Boiler Detected Overview This method uses an RS485 digital communications cable with the Modbus protocol to control a boiler or SmartCycle network Theboilerorboilernetworkwil...

Страница 15: ...of seconds that the boiler has been running For instance Register 29 65536 Register 30 Boiler 1 runtime in seconds Boiler 1 is the master boiler Boilers 2 16 are member boilers 0 4294967295 seconds BA...

Страница 16: ...connection as shown in Fig ure 12 Install a fused service switch mounted and installed in accordance with all appli cable codes 1 2 3 4 5 6 7 8 9 1 1 2 3 Figure 11 Electrical connection board see item...

Страница 17: ...ntial damage from heat pocketing in the top of the heat exchanger Thepostpurgecirculatorisfactory pipedandpre wired Do not change the usage the wiring the location or the piping Boiler circulator See...

Страница 18: ...ach boiler requires a return water temperature sensor DHW wiring ONLY if using DHW override mode The boiler or boilers must be piped with isolation valves and wired for override operation Override of...

Страница 19: ...72 Copyright 2008 Mestek Inc Cast iron condensing boiler Cast iron condensing boiler Control manual Method 3 External 4 20ma control continued 3 Figure 16 200i wiring summary wiring to electrical conn...

Страница 20: ...ast iron condensing boiler Cast iron condensing boiler Control manual Method 3 External 4 20ma control continued 3 Figure 17 200i wiring summary wiring to electrical connection board continued see Fig...

Страница 21: ...erminals This will prevent the boiler for attempting to cycle during the setup process See Control menus and adjustments beginning on page 22 for a complete list of control parameters and explanations...

Страница 22: ...e of the display as shown providing information on various setpoints and parameters The display LOC SET means the setpoint temperature Figure 18 shows the fac tory default values Accessing setup menus...

Страница 23: ...P 20 F LO IAR 40 VIEW IARVALUES Display only not changeable here shows values for 8 zones 70 70 70 70 70 70 70 70 OUTDOOR AIR OA SHUTDOWN OFF ON or OFF OA SHUTDOWN OFF OA SETPT 68 F 40 to 100 F OA SET...

Страница 24: ...inutes 0 to 15 minutes 2 MINUTES 0 SECONDS MOD DELAYTIME 10 seconds 0 to 60 minutes 0 MINUTES 10 SECONDS MOD MAX LAST 50 25 to 100 STOP MOD MAX 50 STOP BAND OFSET 5 F 0 to 50 F EARLY STOP 5 BLR STARTT...

Страница 25: ...r temperature when the DHW Demand terminals see a closed contact DHW tank temperature control calls for heat for example OP LIMIT SETPOINTS This is the temperature at the boiler outlet or header senso...

Страница 26: ...ly water temperature High water at low outside air means the design water temperature for maximum load at ODT or outside design temperature for the installation The other end of the reset curve is the...

Страница 27: ...ivate its end switch SYSTEM CLOCK Set the system clock time day of week month day and year on start up and after any power outage to ensure the data log time stamp information will be accurate LOCAL A...

Страница 28: ...should generally be left at factory default BAND ADVANCED SETUP MODULATION PID This parameter should generally be left at factory default ROTATION ADVANCED SETUP FIRING MODE Select the rotation method...

Страница 29: ...ogram will start and show an option screen Select Install USB Drivers to install the program onto the computer After the USB driver installation is complete select Install Firmware Update Plug a USB c...

Страница 30: ...rrow keys to scroll through the log entries entry number and date are on the first line of the log screen Each log entry includes three screens as described below The top line remains the same in all...

Страница 31: ...ntactors or other devices connected to it If all grounding is correct there may be an issue with radiated or induced electrical noise interference Thismaybecausedbyarcingacrossacontactor scontactswhen...

Страница 32: ...TER boiler to act as a MASTER the header sensor must be set to TYPEZ and there must be a header sensor present At power up the header sensor is auto detected If the temperature of the header sensor at...

Отзывы: