background image

11

P/N 42-9472 Copyright 2008 Mestek, Inc.

Cast iron condensing boiler

 

Cast iron condensing boiler

 — Control manual

External interlocks

Wire external limits and fl ow switch, when used, as shown in Figure 8, page 10.
If wiring to and from a motorized combustion air damper, follow the guidelines 
given in Figure 8, page 10. Connect only to the master boiler.

  If any of the member boilers is to operate in override mode, and the 

system is equipped with a combustion air damper, you must provide 
special wiring in order to ensure the damper opens and proves when 
the boiler fi res. Th is must be done without compromising the wiring 
between the master boiler and the damper.

Overrides — Control priorities

Th e 200i control can provide override operation for any or all member boilers in a 
SmartCycle network. Th is requires the boilers be piped with appropriate isolation 
piping and controls.
Override is done by closing a contact across the Heat Demand or DHW Demand 
terminals of any boiler. Th ese priority inputs override all network controls or 4-
20mA input controls to the boiler.

DHW Demand

 — Th e DHW Demand closure takes priority for ALL boilers, in-

cluding the master and all members. When DHW Demand closes, the boiler or 
boilers immediately switch to DHW operation, including sett ing the water tem-
perature to the DHW Setpoint.

Space heating, Heat Demand 

— If any member boiler sees closure across its 

Heat Demand terminals it will begin operation in space heating mode indepen-
dently of commands from the master boiler or 4-20mA input source.

  Do not wire boilers for override operation unless the piping design 

provides automatic isolation of the overriding boilers. Th e master 
boiler would be unable to properly control system water temperature 
if member boilers were to input heat to the system without control 
from the master. DHW operation, in particular, would raise the supply 
temperature from overriding boilers to the DHW Setpoint.

  Override operation control setup — Boilers must be set up with 

operating parameters necessary during their override operation; i.e., 
local setpoint, DHW setpoint, etc.

Summary — priority sequence is:

Priority 1 = DHW Demand

Priority 2 = Heat Demand

Priority 3 = SmartCycle input

Set termination DIP switches

Th e SmartCycle network needs to recognize the beginning and end of the 
network. Th is requires sett ing the four DIP switches on each boiler’s electrical 
connection board.
See Figure 9 for location of the switches. 
See Table 1 for required sett ings. Th e table gives sett ings for SmartCycle modula-
tion — local control and for remote control from a building management system 
(Modbus protocol).
DO NOT connect the communications cables (or shielded wires) between boilers 
until all boilers have had parameters set and then been started up following all in-
structions in the 200i Boiler manual.

1.
2.

3.

4.

5.

6.

7.

1.

2.
3.

4.

Figure 9  

Termination DIP switches (see item 7, Figure 7, 
page 9 for location)

Table 1  

Termination DIP switch settings

Boiler

SmartCycle

Modbus 

(see note)

Master

Switch 1:  ON

Switch 2:  ON

Switch 3:  OFF

Switch 4:  OFF

Switch 1:  ON

Switch 2:  ON

Switch 3:  ON

Switch 4:  ON

Last member

Switch 1:  ON

Switch 2:  ON

Switch 3:  OFF

Switch 4:  OFF

Switch 1:  ON

Switch 2:  ON

Switch 3:  OFF

Switch 4:  OFF

Other members

Switch 1:  OFF

Switch 2:  OFF

Switch 3:  OFF

Switch 4:  OFF

Switch 1:  OFF

Switch 2:  OFF

Switch 3:  OFF

Switch 4:  OFF

Note: Modbus setup is for applications controlled by a building management system. For 
systems using BACnet or LonWorks, a bridge board is used to interface with the 200i 
control. Th e switch is “on” when in the down position and “off  ” when in the up position.

Method 1:  SmartCycle modulation – local control 

(cont.)

1

Содержание 200i

Страница 1: ...ed with a dust freeairsupply Followtheinstructionmanualprocedurestoductairtotheboilerairintake Iftheboilerhasbeencontaminatedbyoperation with contaminated air follow the instruction manual guidelines...

Страница 2: ...nput from an external controller The control method used by the SmartCycle control is based on digital communications which elimi nates the need for analog control signals Analog signalinputs are supp...

Страница 3: ...ernal high limit and or low water cutoff if desired To flow switch when used Used to activate combustion air damper if desired To combustion air damper proving switch required when controlling combust...

Страница 4: ...4 P N 42 9472 Copyright 2008 Mestek Inc Cast iron condensing boiler Cast iron condensing boiler Control manual The Mestek 200iboiler with SmartCycleTM control...

Страница 5: ...Each boiler requires the RS485 interface board and cable Boiler setup is essentially the same as for method 1 with the exception that each boiler must be assigned both a SmartCycle network address and...

Страница 6: ...inFigure2 Install a fused service switch mounted and installed in accordance with all appli cable codes 1 2 3 4 5 6 7 8 9 10 1 1 2 3 Figure 1 Electrical connection board see item 10 page 3 for locatio...

Страница 7: ...potential damage from heat pocket ing in the top of the heat exchanger Thepostpurgecirculatorisfactory pipedandpre wired Do not change the usage the wiring the location or the piping Boiler circulato...

Страница 8: ...ard If there is more than one transformer provide one wire from each transformer common side to one of the IAR negative terminals IAR Sensor wiring Header sensor is required A header sensor must be in...

Страница 9: ...8 Mestek Inc Cast iron condensing boiler Cast iron condensing boiler Control manual Figure 7 200i wiring summary wiring to electrical connection board Method 1 SmartCycle modulation local control cont...

Страница 10: ...sing boiler Cast iron condensing boiler Control manual Figure 8 200i wiring summary wiring to electrical connection board continued see Figure 7 page 9 for terminal strip locations Also see Figure 5 p...

Страница 11: ...trol system water temperature if member boilers were to input heat to the system without control from the master DHW operation in particular would raise the supply temperature from overriding boilers...

Страница 12: ...s Carefully read the parameter explanations in Table 8 page 25 through page 29 When adjusting the limit band operating limit OP LIMIT local setpoint LOC SETPOINT and DHW setpoint make sure the operati...

Страница 13: ...C 13 D 14 E and 15 F If the display shows a blank space such as 123_56789ABC the control does not detectthemissingboiler boiler4 ChecktheyellowLEDonthecommunication port of the missing boiler NORMAL c...

Страница 14: ...r 15 MainValve 31 Present Boiler Detected Overview This method uses an RS485 digital communications cable with the Modbus protocol to control a boiler or SmartCycle network Theboilerorboilernetworkwil...

Страница 15: ...of seconds that the boiler has been running For instance Register 29 65536 Register 30 Boiler 1 runtime in seconds Boiler 1 is the master boiler Boilers 2 16 are member boilers 0 4294967295 seconds BA...

Страница 16: ...connection as shown in Fig ure 12 Install a fused service switch mounted and installed in accordance with all appli cable codes 1 2 3 4 5 6 7 8 9 1 1 2 3 Figure 11 Electrical connection board see item...

Страница 17: ...ntial damage from heat pocketing in the top of the heat exchanger Thepostpurgecirculatorisfactory pipedandpre wired Do not change the usage the wiring the location or the piping Boiler circulator See...

Страница 18: ...ach boiler requires a return water temperature sensor DHW wiring ONLY if using DHW override mode The boiler or boilers must be piped with isolation valves and wired for override operation Override of...

Страница 19: ...72 Copyright 2008 Mestek Inc Cast iron condensing boiler Cast iron condensing boiler Control manual Method 3 External 4 20ma control continued 3 Figure 16 200i wiring summary wiring to electrical conn...

Страница 20: ...ast iron condensing boiler Cast iron condensing boiler Control manual Method 3 External 4 20ma control continued 3 Figure 17 200i wiring summary wiring to electrical connection board continued see Fig...

Страница 21: ...erminals This will prevent the boiler for attempting to cycle during the setup process See Control menus and adjustments beginning on page 22 for a complete list of control parameters and explanations...

Страница 22: ...e of the display as shown providing information on various setpoints and parameters The display LOC SET means the setpoint temperature Figure 18 shows the fac tory default values Accessing setup menus...

Страница 23: ...P 20 F LO IAR 40 VIEW IARVALUES Display only not changeable here shows values for 8 zones 70 70 70 70 70 70 70 70 OUTDOOR AIR OA SHUTDOWN OFF ON or OFF OA SHUTDOWN OFF OA SETPT 68 F 40 to 100 F OA SET...

Страница 24: ...inutes 0 to 15 minutes 2 MINUTES 0 SECONDS MOD DELAYTIME 10 seconds 0 to 60 minutes 0 MINUTES 10 SECONDS MOD MAX LAST 50 25 to 100 STOP MOD MAX 50 STOP BAND OFSET 5 F 0 to 50 F EARLY STOP 5 BLR STARTT...

Страница 25: ...r temperature when the DHW Demand terminals see a closed contact DHW tank temperature control calls for heat for example OP LIMIT SETPOINTS This is the temperature at the boiler outlet or header senso...

Страница 26: ...ly water temperature High water at low outside air means the design water temperature for maximum load at ODT or outside design temperature for the installation The other end of the reset curve is the...

Страница 27: ...ivate its end switch SYSTEM CLOCK Set the system clock time day of week month day and year on start up and after any power outage to ensure the data log time stamp information will be accurate LOCAL A...

Страница 28: ...should generally be left at factory default BAND ADVANCED SETUP MODULATION PID This parameter should generally be left at factory default ROTATION ADVANCED SETUP FIRING MODE Select the rotation method...

Страница 29: ...ogram will start and show an option screen Select Install USB Drivers to install the program onto the computer After the USB driver installation is complete select Install Firmware Update Plug a USB c...

Страница 30: ...rrow keys to scroll through the log entries entry number and date are on the first line of the log screen Each log entry includes three screens as described below The top line remains the same in all...

Страница 31: ...ntactors or other devices connected to it If all grounding is correct there may be an issue with radiated or induced electrical noise interference Thismaybecausedbyarcingacrossacontactor scontactswhen...

Страница 32: ...TER boiler to act as a MASTER the header sensor must be set to TYPEZ and there must be a header sensor present At power up the header sensor is auto detected If the temperature of the header sensor at...

Отзывы: