OFF RATE PERCENT 30
Used to set the percent of off target value. Alarm sounds when the actual rate
is off from the target rate by a specified percent. The off target value is preset
to 30%, but may be changed to a different number.
a)
Display will show
OFF RATE PERCENT 30
. Press
.
b)
Display will show
OFF RATE PERCENT E
. Enter new off rate percent and
press .
c)
Momentarily depress
to advance to HIGH PWM OFFSET 253.
15)
HIGH PWM OFFSET 253
Used to set the maximum desired RPM or hydraulic output of control valve.
a)
Display will show
HIGH PWM OFFSET 253
.
b)
Place product switch on MAN, boom switches and master switch ON. Hold
INC/DEC switch to increase. If motor exceeds desired RPM, decrease number
by 10 and push INC again.
c)
Decrease the 253 number displayed until motor runs at desired maximum RPM,
then enter a number of 10 more.
d)
Momentarily depress
to advance to LOW PWM OFFSET 1.
16)
LOW PWM OFFSET 1
Used to set the minimum desired RPM or hydraulic ouput of control valve. Used
to set the zero point or shut-off point of control valve.
a)
Display will show
LOW PWM OFFSET 1
.
b)
Place product switch on MAN, boom switches and master switch ON. Hold
INC/DEC switch to decrease until motor stops. Increase the number dis-
placed until motor runs, then enter a number of 10 less.
c)
Hold INC/DEC switch to decrease. If motor does not stop, lower offset
number by 10 and push DEC switch again.
d)
Momentarily depress
to advance to PWM FREQUENCY 122.
17)
PWM FREQUENCY 122
a)
Display will show
PWM FREQUENCY 122
.
b)
Press . Enter the coil frequency of the PWM valve being used
(i.e. 180 Hz). Press
, depress
again.
c)
Momentarily depress
to advance to DATA-LOCK.