Chapter 6: DPX Series
59
Connecting Detectors/Switches to DPX-CC2-TR
DPX-CC2-TR comprises two parts: sensor box and terminal module. The
terminal module is detachable so it is convenient to connect/disconnect
discrete detectors/switches.
Below are the resistance values for DPX-CC2-TR to open and close a
connected detector/switch reliably.
Open: Greater than 320K ohm
Closed: Less than 200K ohm
To make connections when the terminal module is attached:
1.
Strip the insulation around 12 mm from the end of each wire of
discrete detectors/switches.
2.
Fully insert each wire of both detectors/switches into each
termination point.
Plug both wires of a detector/switch into the two termination
points to the left.
Plug both wires of the other detector/switch into the two
termination points to the right.