78
This section shows the factory specifications of Raritan DPX, DPX2 and
DX2 environmental sensor packages. Calibration is not required for
these sensor packages.
In This Chapter
DPX Sensor Accuracy ................................................................................ 78
DPX2 Sensor Accuracy .............................................................................. 78
DX2 Sensor Accuracy ................................................................................ 78
DPX Sensor Accuracy
Temperature: +/-2 degrees Celsius (+/-3.6 degrees Fahrenheit)
Humidity: +/-5% (when humidity < 60%) or +/-8% (when humidity >
60%)
Differential air pressure: +/-1.5%
Air flow: +/-6.5%
DPX2 Sensor Accuracy
Temperature: +/-1.0 degree Celsius (+/-1.8 degrees Fahrenheit)
Humidity: +/-2.5% (when humidity = 10% to 90%)
DX2 Sensor Accuracy
Temperature: +/-1.0 degree Celsius (when temperature = 20 to 70
degrees Celsius)
+/-1.0 degree Celsius is equal to +/-1.8 degrees Fahrenheit
Humidity: +/-2.5% (when humidity = 10% to 90%)
Appendix C Sensor Measurement Accuracy