Chapter 6: DPX Series
56
Connecting a DPX Sensor Package to an Air Pressure Sensor
You can add any DPX sensor package to a differential air pressure
sensor.
To connect one DPX to one air pressure sensor:
1.
Use a Raritan-provided phone cable to connect an air pressure
sensor to a Raritan or Legrand product.
a.
Plug one end of the cable into the sensor's "In" port.
b.
Plug the other end into a Raritan or Legrand product's sensor
port.
An RJ-12 to RJ-45 adapter is required if your Raritan PDU has an
RJ-45 SENSOR port, such as PX3.
2.
Connect one DPX sensor package to the air pressure sensor's "Out"
port.
It can be any available DPX sensor package shown in the section
titled
Available DPX Sensor Packages
(on page 52).
Note: You CANNOT cascade more than two sensor packages in this DPX
sensor chain.