INSTALLATION INSTRUCTIONS  

FOR OEM USE ONLY

© 2016 Mertik Maxitrol GmbH & Co. KG, 

All Rights Reserved.

Pilot Flame Adjustment

(Vented Units Only)

The pilot flow adjustment is preset to maximum at the factory. 

The pilot flame should envelope ⅜ʺ to ½ʺ of the thermocouple 

(see figure 22).

1.  The adjustment screw can be reached through a hole in the 

MANUAL knob (see figure 21).

2.  Turn the MANUAL knob to the 

ON

 position.

3.  It is now possible to pierce through a film on the cover with a 

screwdriver to reach the adjustment screw beneath.

4.  Turn the adjustment screw clockwise 

 to decrease or 

counterclockwise 

 to increase pilot flame.

Outlet Pressure Adjustment

(Vented Units Only)

STANDARD REGULATOR OR THROTTLE

(Throttle CE Only)

1.  Connect a pressure manometer to the valve outlet pressure 

tap. Pressure tap is opened by turning the screw counterclock-

wise 

.

   Pressure regulator or throttle are located under the cover and 

can be reached by removing the plug (see figures 21 and 23).

2.  Turn MANUAL knob and main valve knob to the 

ON 

position.

3.  Turn pressure regulator adjustment screw to set required 

burner pressure (high fire). Pressure is increased by turning 

clockwise 

 (pressure regulator models), or decreased by 

turning counterclockwise 

.

Vented Gas Appliances

Figure 22: Proper Flame Impingement on Thermocouple

Figure 21: GV60, Connections and Adjustment Options

Side Outlet

Side Inlet

Main Valve Knob

Manual Knob

Bottom 

Outlet

Bottom 

Inlet

Pressure Regulator

(remove plug first)

Inlet Pressure Tap

Outlet Pressure Tap

Pilot Gas Adjustment

Screw (turn with screw-

driver)

Magnet Unit

Minimum Rate Orifice

Connection 

Piezo Igniter

Tab 2.8 x 0.8 mm

NOTE:

 

 Throttle model’s pressure is increased by turning coun-

terclockwise 

;  or  decreased  by  turning  clockwise 

.

4. After adjustment, replace the plug.

5.  If no other adjustments are required, close pressure tap(s) by 

turning the screw(s) full clockwise 

.

  Check all connections / pressure tap(s) for leaks.

6.  If the desired outlet pressure or flow cannot be achieved by 

adjusting the gas valve, check the gas valve inlet pressure us-

ing a manometer at the valve inlet pressure tap. If the inlet 

pressure is in the normal range, replace the gas valve; other-

wise, take necessary steps to assure proper gas pressure to 

the valve.

CONVERTIBLE PRESSURE REGULATOR

(CSA Only; Optional)

Convertible regulators are designed to deliver either of two fixed 

outlet pressures for Natural Gas (NG) or LP Gas. To change 

from one gas to the other, turn the conversion plug (see figure 

24, page 14) counter clockwise to remove. Unsnap and remove 

the plastic part, rotate it 180°, and then slide it back on the con-

version plug until it snaps. Turn the conversion plug clockwise 

until it bottoms out. 

Knob function as follows (see figure 21):

KNOB

POSITION

FUNCTION

Main valve knob

OFF

Prevents main gas flow through valve.

Main valve knob

ON

Permits main gas flow through valve 

if the pilot is lit and thermocouple is 

generating sufficient power.

Manual knob

MAN

Allows the pilot to be manually ignited 

and prevents main gas flow.

Manual knob

ON

Allows for automatic ignition.

KNOB SETTINGS

ADJUSTMENT

Figure 23: Combination Control GV60, Cover

Pressure Regulator or Throttle

It is the appliance manufacturer’s responsibility to determine 

GV60’s suitability for a specific application.

Do not attempt to remove screws from the top of gas valve. 

Do not change any adjustments marked with tamper indicating 

paint. Motor knob is not to be removed.

⅜ to ½ in.

(10 to13 mm)

Thermocouple

NOTE:

 Components are not actual size.

Содержание VIVA L Series

Страница 1: ...ecter l appareail et remplacer toute partie du syst me de commande et toute commande qui a t plong e dans eau Attention Au moment de l entretien des com mandes tiquetez tous les fils avant de les d br...

Страница 2: ...valve during any pressure testing of the gas supply piping system at test pressures equal to or less than 1 2 psi 3 5 kPa The installation must provide for adequate ventilation air to the appliance T...

Страница 3: ...ropane LP Input Rating Btu hr 31 000 25 600 Min Input Btu hr 8 000 8 000 Orifice Marking Front 120 80 Orifice Marking Rear 260 x2 100 x2 GAS SUPPLY Manifold Pressure 4 0 w c 1 0kPa 10 8 w c 2 7kPa Min...

Страница 4: ...ct must be installed by a licensed plumber or gas fitter when installed within the Commonwealth of Massachusetts If this appliance is installed in a dwelling building or structure used in whole or in...

Страница 5: ...s specific installation requirements that must be followed to insure a safe and functional venting system for your VIVA L SEE PAGE 13 FOR INFORMATION ABOUT REAR VENTING DIRECTLY THROUGH THE WALL TO A...

Страница 6: ...x8 Expander may be used so that 5x8 flue can be used thereafter Flue Terminal 4x6 Alternatively 5x8 Minimum Vertical Flue Height 20 0 5m Flue Restrictors to be fitted 4x6 Vertical Rise 3 feet 1m No Re...

Страница 7: ...13 Vertical Roof Termination on angle 14 Vertical Roof Termination with bends...

Страница 8: ...CTLY THROUGH THE WALL TO A STANDARD HORIZONTAL VENT TERMINATION The Viva L Gas Stove can be vented in rear exit with up to 18 of horizontal pipe and no vertical pipe util izing a standard horizontal v...

Страница 9: ...sure all four leveling bolts are screwed in all the way They can be adjusted later See the illustration below for leveling bolt locations Move the VIVA L to location where it will be installed Using a...

Страница 10: ...area clear Position the 8 logs as shown noting the 2 special logs labelled A and B These have a slot cast into the underside this slot fits on top of the 2 raised burner sections Lay the glow strands...

Страница 11: ...ery important Take care in handling these gaskets as they will be re used They are somewhat fragile and will tear if handled roughly Next break out the rear exit cover plate from the rear plate Remove...

Страница 12: ...and or installing of gas piping should only be performed by a qualified individual Schedule 40 Black Iron Pipe Inside Diameter Inches Schedule 40 Pipe Natural Propane Length feet Gas Gas 0 10 10 40 4...

Страница 13: ...LIGHTING THE FIRE FOR YOUR SAFETY READ BEFORE LIGHTING WARNING If you do not follow these instructions exactly a fire or explosion may result causing property damage personal injury or loss of life 2...

Страница 14: ...24 25...

Страница 15: ...26 27...

Страница 16: ...ility of the manufacturer INSPECT the external vent cap on a regular basis to make sure that no debris plants trees shrubs are interfering with the air flow CLEANING THE GLASS WARNING Never clean the...

Страница 17: ...ANER TO CLEAN THE LOGS OR BURNER A vacuum cleaner may be used to clean the metal parts of the firebox Replace the logs and embers after cleaning Follow the instructions on pages 18 21 of this manual t...

Страница 18: ...available will greatly expedite trouble shooting should any problem arise with your stove The installer should keep a duplicate of this form for their records Manufactured by RAIS A S Industrivej 20...

Страница 19: ...31 Viva 100 LG with side glass 32 Viva 120 L without side glass...

Страница 20: ...33 Viva 120 LG with side glass 34 Viva 160 L without side glass...

Страница 21: ...35 Viva 160 LG with side glass 36 Appendix 2 Mertik Symax controls...

Страница 22: ...atic Shut Off 33 INSTALLATION INSTRUCTIONS Application 3 Components 3 Technical Specifications 4 Mounting Positions 5 Gas Connections 5 Perform Gas Leak Test 6 Wiring 6 Basic 8 Additional Function 9 2...

Страница 23: ...not try to repair it Call a qualified service technician Force or attempted repair can result in a fire or explosion Do NOT use a product if you suspect it has been subjected to high temperatures dama...

Страница 24: ...BU E Figure 6 2nd Thermocouple Option Figure 5 Mains Adapter Receiver B6R R8 9 PT 2nd Thermocouple Cable G60 ZCTC 2000 Figure 1 Handsets Figure 3 Basic Thermocurrent Cable Interrupter Block Receiver...

Страница 25: ...d Consult the dealer or an experienced radio TV technician for help POWER SUPPLY Handset 2 x 1 5V AAA quality alkaline recommended Receiver 4 x 1 5V AA quality alkaline recommended AnAC mains adapter...

Страница 26: ...nnections Overtightening can damage the control body resulting in a leak or a control malfunction see MAXIMUM ALLOWED TORQUE page 4 Main Gas Tubing Connections 1 Do not use pipe joint compound Mertik...

Страница 27: ...re 13 After successful synchroniza tion the current state of the gas fire is displayed on the handset Main Gas Pipe Connections 1 Mertik Maxitrol does NOT recommend the use of Teflon PTFE tape 2 Pipe...

Страница 28: ...ransfer Press reset button on the myfire Wi Fi Box for 1 second to change current channel NOTICE If myfire Wi Fi Box is not connected to the receiver or is not used it will leave the Access Point Mode...

Страница 29: ...k G60 ZUS Mains Adapter optional G60 ZMA3 Ignition Cable G60 ZKIS RESET Button Additional functions The receivers can be used to start a power flue control 2pin outlet or to operate a second burner or...

Страница 30: ...erated in accordance with all codes and local regula tions Service and installation must be performed by a trained experienced service technician D o not use the module if you suspect it may be damage...

Страница 31: ...inal of the G60 ZCTCR 2000 cable into the open connector hole of the plug see image 1 Listen for a click 3 I nsert the insulated receptacle into the insulated 2 nd thermocouple terminal 4 Insert the p...

Страница 32: ...has to close both burners If the Solenoid Valve is installed upstream of the valve a pilot gas position would not be possible Solenoid Valve Required for Power Flue Control Gas Combination Control GV...

Страница 33: ...R ZWSE N Mains Adapter G60 ZMA3 115 230 V AC Cable G60 ZCSW1000 myfire Wi Fi Box B6R W Receiver B6R R8 9 P B6R R8 9 PT Main Burner myfire App for Android iOS Handset B6R H8 9 P Light Fan Relay with Ca...

Страница 34: ...NOTE Throttle model s pressure is increased by turning coun terclockwise or decreased by turning clockwise 4 After adjustment replace the plug 5 If no other adjustments are required close pressure ta...

Страница 35: ...a custom er specific setting are factory set at maximum flow 3 Turn the screw clockwise to decrease the minimum flow 4 Care should be taken to screw the fixed orifice until it stops 5 Close pressure t...

Страница 36: ...Low battery indication frequent beeps for 3 seconds when mo tor turns An AC mains adapter may be used instead of batteries The V module for fan speed control and light dimmer provides the receiver wi...

Страница 37: ...process The home screen is displayed and the myfire app is ready to go NOTICE The active device Symax handset or smart device is the one last used An exception is if the non active devise is used to...

Страница 38: ...ess or but ton 7 To confirm press and buttons simultaneously or wait CHILD PROOF 1 2 ON AM PM OFF ON To activate press and buttons simultaneously displayed and the handset is rendered inoperable excep...

Страница 39: ...or high fire and low fire double click operation AM To go to low fire double click but ton is displayed NOTE Flame goes to high fire first be fore going to low fire AM To go to high fire double click...

Страница 40: ...d nesday Thursday Fri day Sat urday Sunday 3 Press and buttons simultane ously Hour flashes 4 To select hour press or button 5 Press and buttons simultane ously Minutes flash 6 To select minutes press...

Страница 41: ...me TO TURN OFF FIRE 1 2 ON AM PM OFF Handset Press button to turn off NOTE A new ignition is possible after the OFF icon stops flashing FLAME HEIGHT ADJUSTMENT 1 2 ON AM PM OFF Handset To increase fla...

Страница 42: ...ct off temperature by pressing the or button 4 To confirm press button NOTE The on Thermostatic and off set temperatures are the same for each day 1 2 ON AM PM OFF DAY SETTING 5 flashes Press or butto...

Страница 43: ...nd or off tem perature has been set that temperature becomes the new default setting NOTE If or Daily Timer are programmed for PRO GRAM 1 and PROGRAM 2 on and off times these be come the new default t...

Страница 44: ...y Wed nesday Thursday Fri day Sat urday Sunday 3 Press and buttons simultane ously Hour flashes 4 To select hour press or button 5 Press and buttons simultane ously Minutes flash 6 To select minutes p...

Страница 45: ...TURN OFF FIRE 1 2 ON AM PM OFF Handset Press button to turn OFF NOTE A new ignition is possible after the OFF icon stops flashing FLAME HEIGHT ADJUSTMENT 1 2 ON AM PM OFF Handset To increase flame he...

Страница 46: ...flashes Press or button to choose between 6 To confirm press button MODES of OPERATION 1 2 ON AM PM OFF Thermostatic Mode The room temperature is measured and compared to the set temperature The flam...

Страница 47: ...flashes 8 To select hour press or button 9 To confirm press button displayed displayed shortly and minutes flash 10 To select minutes press or but ton 11 To confirm press button OFF TIME SETTING PROG...

Страница 48: ...day Sat urday Sunday 3 Press and buttons simultane ously Hour flashes 4 To select hour press or button 5 Press and buttons simultane ously Minutes flash 6 To select minutes press or but ton 7 To confi...

Страница 49: ...TURN OFF FIRE 1 2 ON AM PM OFF Handset Press button to turn off NOTE A new ignition is possible after the OFF icon stops flashing FLAME HEIGHT ADJUSTMENT 1 2 ON AM PM OFF Handset To increase flame he...

Страница 50: ...FF DAY SETTING 5 flashes Press or button to choose between 6 To confirm press button MODES of OPERATION 1 2 ON AM PM OFF Thermostatic Mode The room temperature is measured and compared to the set temp...

Страница 51: ...1 7 displayed is displayed shortly and hour flashes 8 To select hour press or button 9 To confirm press button displayed displayed shortly and minutes flash 10 To select minutes press or but ton 11 To...

Страница 52: ...ght works independently of the Pilot flame If you want the light on but no flame press button MYFIRE APP NOTICE Before theApp can be used the myfire Wi Fi Box must be wired and plugged into mains powe...

Страница 53: ...ut tons to switch Decorative Burner on NOTE The latching solenoid valve cannot operate manually If the receiver battery runs down it will remain in the last operating position SWITCH PANEL Figure 31 S...

Страница 54: ...gnitor optional ON OFF Switch optional in ON Position Connection Piezo Ignitor Tab 2 8 x 0 8 mm TO TURN OFF GAS TO APPLIANCE 1 Place ON OFF switch if equipped in O OFF position 2 If gas control is acc...

Страница 55: ...23555 Telegraph Rd PO Box 2230 Southfield MI 48037 2230 USA Tel 1 248 356 1400 Fax 1 248 356 0829 www maxitrol com Exclusive Distributor Europe for Maxitrol Company Mertik Maxitrol GmbH Co KG Warnsted...

Отзывы: