Trouble Shooting The Gas Control System

NOTE: Before troubleshooting the gas control system, be sure external gas shut off is in the “On” position.

Problem

Possible Causes

Corrective Action

Spark igniter will not light.

Defective or misaligned 

Check for spark at electrode and pilot: if no spark and electrode 

electrode at pilot.

wire is properly connected, replace igniter.

Defective igniter

Using a match, light pilot. If pilot lights, turn off pilot and push 

(push-button)

the red button again. If pilot will not light - check gap at electrode
and pilot should be 1/8” to 1/4” to have a strong spark.

Pilot will not stay lit after carefully

Defective thermocouple

Check pilot flame. Must impinge on generator and thermocouple.

following lighting instructions.

(flame switch where applicable) 

Clean and/or adjust pilot for maximum flame impingement on
generator and thermocouple.  Replace thermocouple if pilot will 
not hold.  (Hand tight 1/8 turn on replacement)

Defective valve magnet.

Replace valve, if pilot won’t hold after the thermocouple is 
replaced.

Pilot burning, no gas to burner,

Wall switch or wires

Check wall switch and wires for proper connections. Jumper wire

Valve knob “ON”, Wall

defective.

across terminals at wall switch. If burner comes on, replace 

Switch “ON”

defective wall switch. If okay, jumper wires, across wall switch 
wires at valve. If burner comes on, wires are faulty or 
connections are bad.

Generator may not be 

Check generator with millivolt meter. Take reading at generator 

generating sufficient voltage.

terminals of gas valve. Should read 325 millivolts minimum while
holding valve knob depressed in pilot position and wall switch 
“off” Replace faulty generator if reading is below specified 
minimum.

Plugged burner orifice.

Check burner orifice for stoppage and remove.

Defective automatic valve

Remove wall switch wires from gas valve. Install jumper wires 

operator.

from top bottom terminals of gas valve. Turn valve on “ON”. If 
main burner does not light, replace valve.

Frequent Pilot outage problem.

Pilot flame may be too low or

Clean and/or adjust pilot flame for maximum flame impingement

blowing (high) causing the pilot

on generator and thermocouple.

safety to drop out.

Flame lifts off burner and goes 

Inner 4” liner has come off flue

Attach 4” liner to flue or termination using      

out in less than 30 seconds

or termination, flame is starving

screws, silicone and clamps as stated in manual

for oxygen

Flame lifts off burner on

Improper installation of firebrick.

Be sure to position firebrick against firebox walls and be sure to 

one side while the rest of

Firebrick is likely leaning.

use brick clips attached to the inner side of firebox.

the flame remains lit.

26

WARNIING: 

BEFORE DOING ANY GAS CONTROL SERVICE WORK, REMOVE THE GLASS FRONT.

Содержание Kingsman Fireplaces FDV350

Страница 1: ...Propane Horizontal installations the venting must be a minimum of one foot vertical off the flue before going horizontal Installation Instructions Model Number FDV350 Free Standing Direct Vent Gas St...

Страница 2: ...the installations e g marble tile and the adhesives used to adhere this product to the walls can react with heat and cause odours It is recommended that you burn your gas fireplace or stove for a mini...

Страница 3: ...Installation of brick panel kit 12 Log assembly 13 Optional fan kit installation 14 Millivolt system lighting burner control 15 Vent termination 16 General venting information 17 Vent pipe assembly 1...

Страница 4: ...ED USING THE B VENT CONVERTER CANNOT BE INSTALLED IN A MANUFACTURED MOBILE HOME Please follow the current ANSI NFPA 70 National Electrical Code in the USA and CAN CSA C22 1 Canadian National Electrica...

Страница 5: ...the appliance 15 Installation and repair should be done by a qualified service person The appliance should be inspected before use and at least annually by a professional service person More frequent...

Страница 6: ...in the living area outside the bedroom s The carbon monoxide detector shall comply with NFPA 720 B A carbon monoxide detector shall be located in the room that houses the appliance or equipment and s...

Страница 7: ...l with no additional floor protection being required This unit has been tested in a Alcove the minimum size of Alcove is Depth 30 Height 55 5 Width 52 5 THE FOLLOWING MINIMUM DISTANCES TO COMBUSTIBLES...

Страница 8: ...n excess of 1 2 PSIG 3 5 KPa 9 The appliance must be isolated from the gas supply piping system by closing its individual shutoff valve during any pressure testing of the gas supply piping system at t...

Страница 9: ...eries Children and adults should be alerted to the hazards of high surface temperatures of this appliance and should stay away to avoid burns or ignition of clothing Control compartments burners and a...

Страница 10: ...er cardboard coal be used in this appliance NOTE it is normal for your gas stove to give off some odour the first time it is burned This is due to the curing of the paint and any undetected oil from t...

Страница 11: ...the Door Frame to the unit reverse the above steps GENERAL GLASS INFORMATION GLASS CLEANING It will be necessary to clean the glass periodically During start up condensation which is normal forms on t...

Страница 12: ...right of panel tilt the top panel towards you slightly and pull your right hand towards you slightly and place panel onto the rear of the firebox NOTE TAKE CARE NOT TO DAMAGE PILOT ASSEMBLY WHEN PLACI...

Страница 13: ...side of the log mounting pan as shown in the picture Fig 5 Log C has to be lowered into position just behind logs A and B Log C has an area notched out of the rear of it to fit over rear positioning b...

Страница 14: ...kwise Use the set screw on the side of the variable speed control to increase or decrease the minimum fan speed It may be desirable to lower minimum fan speed to decrease the sound level created by th...

Страница 15: ...pilot screw to provide proper sized flame Recommended Maximum Lead Length Double Wire When Using Wall Switch or Thermostat Wire Size Max Length 14 GA 100 FT 16 GA 64 FT 18 GA 40 FT 20 GA 25 FT 22 GA...

Страница 16: ...8 inches 45cm N Clearance to perpendicular wall 24 inches 60 cm Recommended to prevent re circulation of exhaust products For additional requirements check local codes V NOTE Clearances are to the edg...

Страница 17: ...fically approved and LABELED for this stove may be used This appliance is also approved for use with Simpson Duravent Direct Vent system Ameri Vent Direct Vent Pipe System ICC Excel Direct Metal Fab S...

Страница 18: ...mum stove performance HOW TO USE THE VENT TABLE 1 Determine the height of the system and the number of elbows required 2 Use the Venting Chart to determine the maximum horizontal distance allowed Tota...

Страница 19: ...ature sealant MIL PAC SEALANT IS RECOMMENDED to the pipe and secure it with the 4 screws If two pieces of 4 flex pipe are to be joined the joint must be siliconed and secured with four screws Before j...

Страница 20: ...only time this may be unavoidable is when installing the vent terminal Note Do not remove or move spacer springs attached to 4 inner flex pipe these must be used to assure an 1 1 4 air gap between 4...

Страница 21: ...to the top of the horizontal pipe must be maintained Maximum vertical height of system should not exceed 40 feet Spacer springs to be installed on 4 flex pipe every 3 ft on vertical runs On 45 elbows...

Страница 22: ...y seated Screw the Converter to the stove with 2 of the 4 screws supplied 3 Place the decorative collar around the adapter and screw in place 4 Route the Safety Spill Switch wires down the rear of the...

Страница 23: ...inch single wall or B Vent liquid fuel gas chimney or Flex Gas Liner may be used to adapt existing chimney or liner to stove When installing with B Vent liquid fuel gas chimney install as per B Vent M...

Страница 24: ...Galvanized Pipe 7 Dia x 48 Vertical Installations ZDV4FP8 Flex Pipe 4 Diameter 4 Unexpanded to 8 Expanded ZDV4FP20 Flex Pipe 4 Diameter 10 Unexpanded to 20 Expanded ZDV4FC Flex Connector 4 Diameter ZD...

Страница 25: ...0633 1001 P634SI VALVE NOVA NG Hl LO 0820634 1001 P216SI THEMOCOUPLE 290 216 FOR 713 714 TOP CON PILOT 1001 P069SI ELECTRODE CABLE 915 069 FOR 713 714 TOP CON PILOT 1001 P167SI ORIFICE 30 LP 977 167 F...

Страница 26: ...itch If okay jumper wires across wall switch wires at valve If burner comes on wires are faulty or connections are bad Generator may not be Check generator with millivolt meter Take reading at generat...

Страница 27: ...s other than in a normal residential environment c damages caused by any unauthorized alteration or repair of the unit affecting its stability or performance d damages caused by improper matching or a...

Отзывы: