4. If optional fan kit has been purchased it should now be installed before stove is placed in its final position.
5. Place stove into position. Determine the lengths of the vertical and horizontal 7" pipes. Cut the 7" pipes to the
correct length assuring that the following conditions have been met:
(i)
The horizontal 7" pipe should not extend past the outer portion of zero
clearance wall sleeve.
(ii) There must be a 1/4" rise per foot on horizontal pipe.
(iii) A clearance to combustibles of 2-1/2" must be maintained on the top of
horizontal pipes.
(iv) The clearance to combustibles above the elbow must be 4 inches.
(v) Clearance of one inch on all other pipes.
Before joining 90° elbow and pipes, apply a bead of high temperature sealant
(Mil Pac)
to crimped end of elbow
or pipe. Join pipes to 90° elbow and secure joints with three (3) sheet metal screws,
pipe should overlap on
connection of each pipe by 1-1/2
".
6. Feed the 4" flex pipe through the 7" pipes. If the 4" flex pipe has been expanded do not try to depress it as this
can obstruct air flow and affect the performance of the unit. The only time this may be unavoidable is when
installing the vent terminal.
Note: Do not remove or move spacer springs attached to 4" inner flex pipe, these must be used to
assure an 1-1/4 " air gap between 4" and 7" pipes. Minimum distance between spacer springs should
be 2 FT, a 90 degree elbow requires a spring at the start of the elbow and the end of the elbow.
7. Position 7" pipes with 4" flex pipes installed into final position being sure to install decorative trim plate and trim
ring. Attach 4" flexible pipe to stove with 1/4" bead of sealant and secure with (4) screws. Attach 7" pipe to stove
with sealant and screws.
8. Expand the 4" flex pipe three inches past the 7" rigid pipe at the vent terminal, just enough to allow for the sealant
and securing with (4) screws to the 4" pipe to the terminal. Attach the vent terminal to 4" flex pipe with (4) screws.
Apply sealant to 7" pipe on terminal and gently push the vent terminal into the horizontal section as straight as
possible. Attach the terminal to the exterior wall with screws provided. Apply caulking between the terminal and
the wall to prevent rain and moisture from entering around the terminal.
9. Support horizontal pipes every three (3) feet (91 cm) with metal pipe straps.
10. Install decorative trim bands at the 7" pipe joints.
20