CONVERTING THE FDV350 DIRECT VENT TO A VENTED FIREPLACE
22
Part # F35BVC
B-VENT CONVERTER INSTRUCTIONS
WARNING: Operation of this appliance when not connected to a properly installed and maintained
venting system or tampering with the blocked vent shutoff system can result in carbon monoxide (CO)
poisoning and possible death.
1.
Place a bead of Black Mil Pac sealant around 4 inch flue collar on the stove.
2.
Position Safety Spill Switch wires to rear of stove and Lower B-Vent Converter onto the 4 and 7 inch collars until
fully seated. Screw the Converter to the stove with 2 of the 4 screws supplied.
3.
Place the decorative collar around the adapter and screw in place.
4.
Route the Safety Spill Switch wires down the rear of the stove as shown in the above diagram
5.
On the rear of the valve there is a blue wire with male female connecter which must be disconnect by pulling apart
very carefully, connect the spill switch wires to the blue wires on the rear of the valve.
6.
The stove has now been converted to a vented appliance. (FV350)
7.
Place approval label on label plate, over top of FDV350 Rating Plate. Be sure to line up so serial number of old
unit is legible.
Correct Draw
Incorrect Draw.
Downdraft
occurring
Decorative Band
Decorative Collar screw