background image

1000-306

Thermalcord for Door Frame

1000-216

On/Off Switch

6000-130

Explosion Felt

2000-080

Thermodisc Fan Sensor

2000-085

Variable Speed Switch (Fan)

1000-134

Explosion Damper (Round)

350-EMBER

Embers

36ZV-P300TD

Spill Switch

S.I.T. Valve System

350-BNGSI

NG BURNER ASSEMBLY

(complete with valve)

350-BLPSI

LP BURNER ASSEMBLY

(complete with valve)

REPLACEMENT PARTS

25

VALVE SYSTEM PARTS

TOP CONVERTIBLE PARTS LIST

1001 -P713SI

PILOT TOP CONVERTIBLE - LP - ASSEMBLED 199.713

1001-P714SI

PILOT TOP CONVERTIBLE - NG - ASSEMBLED 199.714

1001-P633SI

#VALVE NOVA LP Hl-LO 0820633

1001-P634SI

#VALVE NOVA-NG Hl/LO 0820634

1001-P216SI

THEMOCOUPLE - 290.216 (FOR 713 & 714 TOP CON. PILOT)

1001-P069SI

ELECTRODE & CABLE - 915.069 (FOR 713 & 714 TOP CON. PILOT)

1001-P167SI

ORIFICE #30 LP - 977.167 (FOR 713 TOP CON. PILOT)

1001-P165SI

ORIFICE #51 NG - 977.165 (FOR 714 TOP CON. PILOT)

1001-P280SI

ALM. TUBING 24" W/FITTINGS 2.182.280

1001-P144SI

NUT- ELECTRODE UNIVERSAL BUSHING

974 144

1000-214

#PIEZO-IGNITER 1244-17 MARK21

1000-P136WR

#GENERATOR GOA1-524

REPLACEMENT PARTS:

350- P217SI

KNOB EXTENSION 1 1/2 - ON/OFF

350-P218SI

KNOB EXTENSION 1 1/2- Hl/LO

350-310

CERAMIC GLASS FRONT - C/W THERMALCORD (FDV350)

350-309

CERAMIC GLASS SIDE - C/W THERMALCORD (FDV350)

CONVERSION KITS:

350DV-CKNG

CONVERSION KIT - NATURAL GAS - FDV350N

350DV-CKLP

CONVERSION KIT - LIQUID PROPANE - FDV350LP

Содержание Kingsman Fireplaces FDV350

Страница 1: ...Propane Horizontal installations the venting must be a minimum of one foot vertical off the flue before going horizontal Installation Instructions Model Number FDV350 Free Standing Direct Vent Gas St...

Страница 2: ...the installations e g marble tile and the adhesives used to adhere this product to the walls can react with heat and cause odours It is recommended that you burn your gas fireplace or stove for a mini...

Страница 3: ...Installation of brick panel kit 12 Log assembly 13 Optional fan kit installation 14 Millivolt system lighting burner control 15 Vent termination 16 General venting information 17 Vent pipe assembly 1...

Страница 4: ...ED USING THE B VENT CONVERTER CANNOT BE INSTALLED IN A MANUFACTURED MOBILE HOME Please follow the current ANSI NFPA 70 National Electrical Code in the USA and CAN CSA C22 1 Canadian National Electrica...

Страница 5: ...the appliance 15 Installation and repair should be done by a qualified service person The appliance should be inspected before use and at least annually by a professional service person More frequent...

Страница 6: ...in the living area outside the bedroom s The carbon monoxide detector shall comply with NFPA 720 B A carbon monoxide detector shall be located in the room that houses the appliance or equipment and s...

Страница 7: ...l with no additional floor protection being required This unit has been tested in a Alcove the minimum size of Alcove is Depth 30 Height 55 5 Width 52 5 THE FOLLOWING MINIMUM DISTANCES TO COMBUSTIBLES...

Страница 8: ...n excess of 1 2 PSIG 3 5 KPa 9 The appliance must be isolated from the gas supply piping system by closing its individual shutoff valve during any pressure testing of the gas supply piping system at t...

Страница 9: ...eries Children and adults should be alerted to the hazards of high surface temperatures of this appliance and should stay away to avoid burns or ignition of clothing Control compartments burners and a...

Страница 10: ...er cardboard coal be used in this appliance NOTE it is normal for your gas stove to give off some odour the first time it is burned This is due to the curing of the paint and any undetected oil from t...

Страница 11: ...the Door Frame to the unit reverse the above steps GENERAL GLASS INFORMATION GLASS CLEANING It will be necessary to clean the glass periodically During start up condensation which is normal forms on t...

Страница 12: ...right of panel tilt the top panel towards you slightly and pull your right hand towards you slightly and place panel onto the rear of the firebox NOTE TAKE CARE NOT TO DAMAGE PILOT ASSEMBLY WHEN PLACI...

Страница 13: ...side of the log mounting pan as shown in the picture Fig 5 Log C has to be lowered into position just behind logs A and B Log C has an area notched out of the rear of it to fit over rear positioning b...

Страница 14: ...kwise Use the set screw on the side of the variable speed control to increase or decrease the minimum fan speed It may be desirable to lower minimum fan speed to decrease the sound level created by th...

Страница 15: ...pilot screw to provide proper sized flame Recommended Maximum Lead Length Double Wire When Using Wall Switch or Thermostat Wire Size Max Length 14 GA 100 FT 16 GA 64 FT 18 GA 40 FT 20 GA 25 FT 22 GA...

Страница 16: ...8 inches 45cm N Clearance to perpendicular wall 24 inches 60 cm Recommended to prevent re circulation of exhaust products For additional requirements check local codes V NOTE Clearances are to the edg...

Страница 17: ...fically approved and LABELED for this stove may be used This appliance is also approved for use with Simpson Duravent Direct Vent system Ameri Vent Direct Vent Pipe System ICC Excel Direct Metal Fab S...

Страница 18: ...mum stove performance HOW TO USE THE VENT TABLE 1 Determine the height of the system and the number of elbows required 2 Use the Venting Chart to determine the maximum horizontal distance allowed Tota...

Страница 19: ...ature sealant MIL PAC SEALANT IS RECOMMENDED to the pipe and secure it with the 4 screws If two pieces of 4 flex pipe are to be joined the joint must be siliconed and secured with four screws Before j...

Страница 20: ...only time this may be unavoidable is when installing the vent terminal Note Do not remove or move spacer springs attached to 4 inner flex pipe these must be used to assure an 1 1 4 air gap between 4...

Страница 21: ...to the top of the horizontal pipe must be maintained Maximum vertical height of system should not exceed 40 feet Spacer springs to be installed on 4 flex pipe every 3 ft on vertical runs On 45 elbows...

Страница 22: ...y seated Screw the Converter to the stove with 2 of the 4 screws supplied 3 Place the decorative collar around the adapter and screw in place 4 Route the Safety Spill Switch wires down the rear of the...

Страница 23: ...inch single wall or B Vent liquid fuel gas chimney or Flex Gas Liner may be used to adapt existing chimney or liner to stove When installing with B Vent liquid fuel gas chimney install as per B Vent M...

Страница 24: ...Galvanized Pipe 7 Dia x 48 Vertical Installations ZDV4FP8 Flex Pipe 4 Diameter 4 Unexpanded to 8 Expanded ZDV4FP20 Flex Pipe 4 Diameter 10 Unexpanded to 20 Expanded ZDV4FC Flex Connector 4 Diameter ZD...

Страница 25: ...0633 1001 P634SI VALVE NOVA NG Hl LO 0820634 1001 P216SI THEMOCOUPLE 290 216 FOR 713 714 TOP CON PILOT 1001 P069SI ELECTRODE CABLE 915 069 FOR 713 714 TOP CON PILOT 1001 P167SI ORIFICE 30 LP 977 167 F...

Страница 26: ...itch If okay jumper wires across wall switch wires at valve If burner comes on wires are faulty or connections are bad Generator may not be Check generator with millivolt meter Take reading at generat...

Страница 27: ...s other than in a normal residential environment c damages caused by any unauthorized alteration or repair of the unit affecting its stability or performance d damages caused by improper matching or a...

Отзывы: