Instruction Book
56
9828 0934 73
•
The screen shows the first items of a list of all settings. Use the scroll button to see the other items
in the list.
•
Press the Enter button (2); a red selection bar is covering the first item (Language in
use). Use the ↓ key of the Scroll keys to select the setting to be modified and press the
Enter key.
•
A pop-
up screen appears. Use the ↑ or ↓ key to select the required parameter and press the Enter
key to confirm.
Dryer setting
Select the Dryer settings icon as described above and press the Enter button (2). Following screen appears:
(1)
Regulation
(2)
Dryer operation mode
(3)
Flow switch mode
(4)
Dewpoint alarm mode
(5)
Variable dewpoint alarm offset
•
The screen shows the first items of a list of all settings. Use the scroll button to see the other items
in the list.
•
Press the Enter button (2); a selection bar is covering the first item (Dryer operation
mode). Use the ↓ key of the Scroll keys to select the setting to be modified and press
the Enter key.
•
A pop-
up screen appears. Use the ↑ or ↓ key to select the required parameter and press the Enter
key to confirm.
It is possible to program three operation modes:
•
‘Economy’: the set-point for the pressure dew-point is ambient temperature minus 36 °F (20 ˚C)
(minimum set-
point is 37 °F (3 ˚C)).
•
‘Lowest Dewp.’: the set-point for the pressure dew-point is 37 °F (3 ˚C) regardless of
the ambient temperature.
•
‘Max. Saving’: the set-point for the pressure dew-point is ambient temperature minus
27 °F (15 ˚C) (minimum set-point is 39 °F (4 ˚C)).
Automatic restart
•
Select the Automatic restart settings icon as described above and press the Enter button (2).
Following screen appears:
Содержание QED 1050
Страница 2: ......
Страница 4: ...Instruction Book 4 9828 0934 73...
Страница 89: ...Instruction Book 9828 0934 73 89 Dimension drawing of air cooled QED 1050 ES 510 imperial units...
Страница 90: ...Instruction Book 90 9828 0934 73 Dimension drawing of air cooled QED 1050 ES 510 metric units...
Страница 94: ...Instruction Book 94 9828 0934 73 4 2 Installation proposal Example Installation proposal metric unit...
Страница 134: ...02 2021 No 9828 0934 73 Ed 00...