Instruction Book
38
9828 0934 73
3
Controller
3.1 General
Control panel
General description
The electronic regulator automatically controls the dryer, i.e.:
•
keeps the pressure dew-point stable
•
stops the dryer whenever necessary
•
restarts the dryer when required
In order to control the dryer and to read and modify programmable parameters, the regulator has a control
panel provided with:
•
LEDs indicating the status of the dryer
•
a display indicating the operating conditions or a fault
•
keys to control the dryer and to access the data collected by the regulator
•
buttons to manually start and stop the dryer
In general, the regulator has following functions:
•
controlling the dryer
•
protecting the dryer
•
automatic restart after voltage failure (made inactive)
Controlling the dryer
The regulator keeps the pressure dew-point stable at no load by opening or closing the solenoid valve of
the hot-gas by-pass.
In order to keep the condenser pressure constant:
•
For air-cooled versions, the regulator starts and stops the fan motor(s) as necessary.
•
For water-cooled versions, the water regulating valve regulates the cooling water flow.
Protecting the dryer
Shut-down
•
In case the pressure in the refrigerant circuit is too high, the dryer will be stopped.
•
For air-cooled versions, the dryer will also be stopped if there is an overload of a fan motor. Warning.
•
A warning message appears if the electronic water drain is malfunctioning.
Содержание QED 1050
Страница 2: ......
Страница 4: ...Instruction Book 4 9828 0934 73...
Страница 89: ...Instruction Book 9828 0934 73 89 Dimension drawing of air cooled QED 1050 ES 510 imperial units...
Страница 90: ...Instruction Book 90 9828 0934 73 Dimension drawing of air cooled QED 1050 ES 510 metric units...
Страница 94: ...Instruction Book 94 9828 0934 73 4 2 Installation proposal Example Installation proposal metric unit...
Страница 134: ...02 2021 No 9828 0934 73 Ed 00...