A2B4
Short circuit
Short-circuit in motor cable(s) or
motor.
Check motor and motor cable for cabling
errors.
Check motor and motor cable.
Check for an earth fault in motor or motor
cables by measuring the insulation
resistances of motor and motor cable
A581
Fan
Cooling fan feedback missing.
Check fan operation and connection.
Replace fan if faulty.
A5A0
Safe torque off
Programmable
warning
Safe torque off function is active, i.e.
safety circuit signal(s) connected to
connector STO is lost.
Check safety circuit connections.
2310
Overcurrent
Output current has exceeded
internal fault limit. In addition to an
actual overcurrent situation, this fault
may also be caused by an earth
fault or supply phase loss.
Check motor load. Check motor and motor
cable.
Check for an earth fault in motor or motor
cables by measuring the insulation
resistances of motor and motor cable
Check if refrigerant compressor selected is
correct on the drive (from the main screen
press two times "OK" button).
2330
Earth leakage
Drive has detected load unbalance
typically due to earth fault in motor
or motor cable.
Check motor and motor cable for cabling
errors.
Check motor and motor cable.
Check for an earth fault in motor or motor
cables by measuring the insulation
resistances of motor and motor cable
2340
Short circuit
Short-circuit in motor cable(s) or
motor
Check motor and motor cable for cabling
errors.
Check motor and motor cable.
Check for an earth fault in motor or motor
cables by measuring the insulation
resistances of motor and motor cable
3130
Input phase loss
Intermediate circuit DC voltage is
oscillating due to missing input
power line phase or blown fuse.
Check input power line fuses.
Check contactor K1.
Check for loose power cable connections.
Check for input power supply imbalance.
3181
Wiring or earth
fault
Incorrect input power and motor
cable connection (i.e. input power
cable is connected to drive motor
connection).
Check input power connections.
3210
DC link
overvoltage
Excessive intermediate circuit DC
voltage.
Check that the supply voltage matches the
nominal input voltage of the drive.
Check the supply line for static or transient
overvoltage.
Check autotransformer output voltage (if
present).
Содержание QED 1050
Страница 2: ......
Страница 4: ...Instruction Book 4 9828 0934 73...
Страница 89: ...Instruction Book 9828 0934 73 89 Dimension drawing of air cooled QED 1050 ES 510 imperial units...
Страница 90: ...Instruction Book 90 9828 0934 73 Dimension drawing of air cooled QED 1050 ES 510 metric units...
Страница 94: ...Instruction Book 94 9828 0934 73 4 2 Installation proposal Example Installation proposal metric unit...
Страница 134: ...02 2021 No 9828 0934 73 Ed 00...