Section VIII - Technical data
50
Cable section
mm2
Ambient temperature
30°C
40°C
45°C
50°C
55°C
25
< 110 A
< 96 A
< 87 A
< 78 A
< 67 A
35
< 137 A
< 119 A
< 108 A
< 97 A
< 84 A
50
< 167 A
< 145 A
< 132 A
< 119 A
< 102 A
70
< 216 A
< 188 A
< 171 A
< 153 A
< 132 A
95
< 264 A
< 230 A
< 209 A
< 187 A
< 161 A
120
< 308 A
< 268 A
< 243 A
< 219 A
< 188 A
Calculation method for IEC:
Single supply cables (3 PE - configuration (1)):
Add 10 % to the total pump current (ItotPack or ItotFF from the tables)
Install the prescribed fuse on each cable
Parallel supply cable (2 x 3 PE - configuration (2)):
Add 10 % to the total pump current (ItotPack or ItotFF from the tables) and divide by
2
Multiply the ampacity of the cables with 0.8 (see table A.52.17 (52-E1))
Install fuses of half the size of the recommended maximum fuse size on each cable.
When using 2 x 3 PE as in (3):
Add 10 % to the total pump current (ItotPack or ItotFF from the tables) and divide by
√3
Multiply the ampacity of the cables with 0.8 (see table A.52.17 (52-E1))
Fuse size: the recommended maximum fuse size divided by √3 on each cable.
Size of the PE cable:
For supply cables up to 35 mm²: same size as supply cables
For supply cables larger than 35 mm²: half the size of the supply wires
Always check the voltage drop over the cable (less than 5 % of the nominal voltage is
recommended).
Example: Itot = 89 A, maximum ambient temperature is 45 °C, recommended fuse =
100 A
Single supply cables (3 PE - configuration (1)):
I = 89 A + 10 % = 89 x 1.1 = 97.9 A
The table for B2 and ambient temperature = 45 ° C allows a maximum current of 93
A for a 50 mm²cable. For a cable of 70 mm², the maximum allowed current is 118 A,
which is sufficient. Therefore, use a 3 x 70 mm² + 35 mm² cable.
If method C is used, 50 mm² is sufficient. (35 mm² for method F) => cable 3 x 50
mm² + 25 mm².
Parallel supply cable (2 x 3 PE - configuration (2)):
I = (89 A + 10 %)/2 = (89 x 1.1)/2 = 49 A
For a cable of 25 mm², B2 at 45 °C, the maximum current is 63 A x 0.8 = 50.4 A. So
2 parallel cables of 3 x 25 mm² + 25 mm² are sufficient.
Install 50 A fuses on each cable instead of 100 A.
Содержание QCV 045
Страница 2: ...This page intentionally left blank...
Страница 21: ...Section III Installation 21 Dimension drawing QCV 045 QCV 90 vacuum pump...
Страница 22: ...Section III Installation 22 Dimension drawing QCV 220 vacuum pump...
Страница 23: ...Section III Installation 23 Dimension drawing QCLP 90 Overpressure pumps...
Страница 24: ...Section III Installation 24 Dimension drawing QCLP 220 Overpressure pump...
Страница 55: ...Notes 55...
Страница 56: ...E mail info quincycompressor com 2016 Quincy Compressor Website www quincycompressor com All Rights Reserved...