Section VIII - Technical data
48
Earthing
The earthing cable connected to the pump (PE) should be minimum 10 mm2 (according
to EN 60204-1 section 828).
Cable sizing according IEC
The tables below indicate the current carrying capacities of cables for 3 commonly used
installation methods, calculated according to standard 60364-5-52 - electrical
installations of buildings part 5 - selection and erection equipment and section 52 -
current carrying capacities in wiring systems.
The allowed currents are valid for PVC insulated cables with three loaded copper
conductors (maximum conductor temperature 70 °C).
Installation method B2 according table
B.52.1.
Multi-core cable in conduit on a wooden
wall.
Maximum allowed current in function of the ambient temperature for installation method
B2
Cable
section
mm2
Ambient temperature
30°C
40°C
45°C
50°C
55°C
4
< 27 A
< 23 A
< 21 A
< 19 A
< 16 A
6
< 34 A
< 30 A
< 27 A
< 24 A
< 21 A
10
< 46 A
< 40 A
< 36 A
< 33 A
< 28 A
16
< 62 A
< 54 A
< 49 A
< 34 A
< 38 A
25
< 80 A
< 70 A
< 63 A
< 57 A
< 49 A
35
< 99 A
< 86 A
< 78 A
< 70 A
< 60 A
50
< 118 A
< 103 A
< 93 A
< 84 A
< 72 A
70
< 149 A
< 130 A
< 118 A
< 106 A
< 91 A
95
< 179 A
< 156 A
< 141 A
< 127 A
< 109 A
120
< 206 A
< 179 A
< 163 A
< 146 A
< 126 A
Содержание QCV 045
Страница 2: ...This page intentionally left blank...
Страница 21: ...Section III Installation 21 Dimension drawing QCV 045 QCV 90 vacuum pump...
Страница 22: ...Section III Installation 22 Dimension drawing QCV 220 vacuum pump...
Страница 23: ...Section III Installation 23 Dimension drawing QCLP 90 Overpressure pumps...
Страница 24: ...Section III Installation 24 Dimension drawing QCLP 220 Overpressure pump...
Страница 55: ...Notes 55...
Страница 56: ...E mail info quincycompressor com 2016 Quincy Compressor Website www quincycompressor com All Rights Reserved...