-4-
AIR THROWS
--o--o--O--O--O--o--o--
HYDRAULIC RESISTANCES
--o--o--O--O--O--o--o--
SOUND POWER and SOUND PRESSURE LEVELS
973 SERIES CWM (L) ( speed 1 = lowest, 3 = highest)
SOUND POWER LEVELS
SOUND PRESSURE LEVELS
Frequency Hz
MODEL
SPEED
125
250
500
1K
2K
4K
dBA
dBA
NC
55
MIN
36.8
37
39.1
38.8
34.4
31.7
43
25
19
MED
41
43.4
45.8
45.1
39.6
35.4
49
31
25
MAX
46.7
48.6
50.6
50.4
46.6
39
54
37
31
75
MIN
39.1
44.3
47.2
46.8
41.6
40.8
51
33
27
MED
43.8
49.1
51.3
51.3
46.7
39.5
55
37
32
MAX
45.5
50.5
53.7
52.9
48.7
40.8
57
39
34
105
MIN
34.1
38
44
42.3
41
38
48
30
24
MED
42.7
45.8
48.9
49.1
44.2
38.1
53
35
30
MAX
46.4
51.6
54.2
54.2
49.9
42.9
57
40
35
Sound Power Levels obtained in conformance with BS 4196: Part 5: 1981. Values are shown in dB with a standard
reference of 1 pW.
Sound Pressure Levels are dB relative to 2 x 10
-5
N/m
2
and are calculated from results measured in anechoic conditions.
Values relate to a position of 3m away from the centre line of the unit, 1m down.