If, as a result of fitting this kit, more than one supply is taken into a unit, that unit must be marked:-
"Two, (or more if applicable), supplies are taken into this equipment.
Isolate both, (all), before undertaking any maintenance work."
PROGRAMMABLE TIMER KIT 52500151
This kit can be used to give
ON/OFF
switching of the mains voltage control circuits of CWM units
where the total current
does not exceed 3 Amps.
ELECTRIC HEATER CURRENTS CANNOT BE SWITCHED DIRECTLY.
It is not required for CWM L units which have built in timers.
ITEM
QTY
DESCRIPTION
1
1
7 Day Programmable Timer
2
1
In Line Fuse Carrier
3
1
5 Amp Fuse, 1" x 1/4"
4
1
Terminal
PROGRAMMER SPECIFICATION
:
Type:
Digital electronic 230V, 50Hz
Programme:
7 day
Setting Resolution:
1 minute
Selection Switch: "OFF",
"TMD " (TIMED)
"CON " (CONSTANT ON)
"ADV " (ADVANCE)
Max. Switched Current:3 A (fan load)
The timer will accommodate 0.75mm
2
to 2.5mm
2
wires.
Three core cable is required between the timer and the air conditioning unit.
The timer motor must be connected to an uninterrupted supply source.
TIMER MOUNTING
1. Carefully unpack and identify the components.
2. If the unit is to be surface wired, remove the appropriate knockouts in the backplate. Screw the backplate to the
wall with No. 8 wood screws through the fixing holes.
3. If the backplate is to be fixed to a BS4662 single gang plaster depth box, use 3.5mm machine screws.
WIRING FOR ON/OFF SWITCHING
4. a) Wire timer terminal 'L' to unit terminal 2.
b) Use the terminal provided to connect terminal 4 to live (terminal L, remote controller RCC 30 [97200211] ).
c) Wire timer terminal 'N' to unit terminal N
5. Discard the in-line fuse carrier.
6. Plug in the unit and secure the screws.
7. Program as described in the separate timer instructions.