-19-
5m HIGH CONDENSATE PUMP KIT FOR CWM (L) UNITS 55600420
ITEM
QTY
DESCRIPTION
1
1
Pump Assembly
This kit is for use on all versions of CWM and CWM L units and is for condensate removal where a lift of up to 5m is
required.
The pump runs on demand.
A high level alarm will switch off the cooling signal until condensate has dropped below a pre-set level.
It is easier to fit this kit before installing the unit.
IF THE UNIT HAS BEEN INSTALLED, ISOLATE THE SYSTEM BEFORE FITTING THE KIT
.
1.
CABINET REMOVAL
2.
FITTING THE KIT
a)
Fit the pump assembly into its temporary position (Fig.1) by sliding the hooks on the pump assembly bracket into the
cut-outs on the back panel side flange.
Note: This is not the final position, but it makes installation easy.
b)
Fit the sensor/filter inside the drain tray (Fig.2). Do not over tighten the screw.
Fig.1
Fig.2
Содержание CWM 105
Страница 8: ...8 INSTALLATION HANGING RAIL FIXING THE HANGING RAIL HANGING THE UNIT CHASSIS...
Страница 12: ...12...