-24-
This instruction is also applicable to return air sensor spare 04000012S
The sensor can be fitted to the return air inlet to an air conditioning unit to improve operation eg. if the wall thermostat
is placed outside the space being conditioned, or if there is considerable stratification in a room with a high ceiling,
where the wall thermostat would not measure a representative temperature.
ITEM
QTY
DESCRIPTION
1
1
Sensor (4m lead)
2
2
Tie wrap
ISOLATE THE SYSTEM ELECTRICALLY PRIOR TO INSTALLATION OF THE SENSOR
1.
Connect the sensor to terminals B1 and M , as shown (polarity is unimportant).
Changeover to the remote sensor is automatic on power up of the controller.
2.
Tie wrap the sensor to a suitable place in the return airflow, where it will soak in a representative temperature.
3
. After installation, adjust the thermostat to confirm satisfactory operation.
Sensor input B1-M carries mains potential.
If the sensor cable needs to be extended, the cables used must be suitable for mains voltage.
--o--o--O--O--O--o--o--
FAULT FINDING
CONDITION
POSSIBLE CAUSE
ACTION
A
Indoor fan motor will not run
No electric supply at socket or switched fuse
box
Check fuse rating and replace if necessary.
Check for loose electrical connections
Unit wiring fault
Check wiring and connections
Fan motor capacitor defective
Replace if faulty
Fan motor defective
Replace if faulty
B
Inadequate cooling or heating
Dirty coil fins/filter
Clean if blocked
Fan motor not running at required speed
As in section A
Faulty thermostat or incorrectly set
Replace if faulty
C
System runs for long periods and will
not cycle
Unit underrated for conditioned area
Check heat load against capacity
Thermostat not operating correctly
Check wiring, position of phial and operation
D
Noisy unit
Worn motor bearing
Replace motor
Casing or piping vibration
Check cause and rectify
Loose parts or mounting
Find and tighten
Bent fan blade
Replace fan
E
Water leaking from unit
Blocked drain or filter
Clear obstruction
Units with a lift pump or condensate
pump
No supply to pump or loose connection Secure the supply
Pumping slowly
Check drain pipes; if clear, replace pump
Pump windings shorted
Replace pump
Fouled sensor (5m condensate pump
only)
Clean sensor
F Pump always runs
Faulty sensor or pcb
Replace sensor or pcb
G No heating
Controls not set for heating
Reset
Unit wiring fault
Check wiring and connections
Dirty coil fins/filter
Clean
Faulty thermostat
Check for signal; replace if faulty
Faulty heater element
Replace
Faulty heater cutout
Replace, (check for short circuiting)
No heaters/LPHW coil fitted
Fit electric heater or LPHW
Heating valve not operating
Check wiring, actuator
CWM L LED display diagnostics:-
Cool
Dry
Fan
Heat
D
I
4
F
Green
Red
Red
Amber
BLINKS x 4
OFF
OFF
OFF
Room sensor missing
BLINKS x 4
OFF
OFF
OFF
Indoor coil sensor missing
BLINKS x 2
OFF
BLINKS
OFF
Pump fault
--o--o--O--O--O--o--o--