background image

-20-

3.

WIRING

a)

Locate the black, blue and red wires in the unit near the pump  and remove the cover

from the black and blue wires.

b)

Connect:

(i)  Black wire to terminal L on the pcb

      

(ii)  Blue wire to terminal N on the pcb

The plastic cover over the pcb can be removed for convenience: retain the cable tie.

c)

Cut the centre loop of the red wire and strip back both ends by 5mm.  Connect the

bared ends to the black de-mountable plug TB1 (non-polarized) on the pcb.

d)

Fit the spare earth wire (clip fitted) to the back panel side flange.

If the plastic cover was removed, secure in its original position with the original cable

tie.

Unhook the pump assembly and fit in its final position (Fig. 3).

Connect a drain hose to the white connector when installed.

4.

TESTING THE PUMP AND CONTROL

a)

Connect a suitably fused supply to the unit (refer to the unit installation instructions).  Allow approximately one minute

for the controls and sensor to stabilize.

b)

Slowly add water to the condensate tray sump until the pump runs.  Initially the pump will be noisy until the air in the

hose has been expelled.  It is possible that, on this first cycle, the pump will run dry for a short period (indicated by

noise).

c)

Add more water to the sump and the pump will cycle in the normal manner.

d)

With the system in cooling mode, continue adding water to the sump until it reaches the higher of the sensor probes.

The cooling cycle will shut down, and the pump will continue to run until the water has dropped below the level of this

probe.

e)

Replace the cabinet.

Note: Whenever the electrical supply to a unit fitted with a condensate pump and controls is interrupted, a delay of up

to 1 minute will occur before the compressor or the pump will start when the supply is reinstated.

5. TROUBLE SHOOTING

Unit will not cool

No mains supply to the control board

Pump does not run

Fuse on control board blown (T315mA x 20mm)

Sensor disconnected from control board

Cooling is interrupted

Restriction in pump flow allowing level to rise and trip overflow circuit

Check for blockage or kink in hoses

Condensate at high level - tripping overflow circuit

Filter blocked - Remove and clean

Excessive pump noise

Air leak in hoses and/or joints

Pumping without water in sump - control board fault

Loose connection between sensor and control board

Loose fuse, intermittent mains supply to control board

Water syphoning due to lack of air break

6. APPLICATION NOTES

1.

The pump will work against a 5m head.  Flow rate is highest with minimum head.

2.

Long lengths of drain pipe should not be exposed to the outdoor ambient, otherwise freezing of condensate may occur

during winter operation.

3.

It is not advisable to have the outlet of the drain well below the position of the pump, otherwise a syphon effect may open

the pump valves and cause noise by admitting air.

4.

For normal applications, i.e. where the drain is level or above the pump or within 3 feet below it, no extra check valves

are needed; the pump has its own internal check valves.

5.

Ensure that no hose is kinked, as this could seriously affect the pump performance.

6.

Clean the filter at regular intervals.

--o--o--O--O--O--o--o--

Fig.3

Содержание CWM 105

Страница 1: ...tting filters 11 Check list 11 MAINTENANCE User maintenance 12 OPTIONAL CWM wired remote controller RCC 30 13 CONTROLS CWM L infrared remote controller 14 WIRING CWM 15 DIAGRAMS CWM L 15 OPERATING CWM...

Страница 2: ...223 WEIGHT kg 19 23 27 PACKED DIMENSIONS AND WEIGHTS Model CWM L 55 75 105 HEIGHT mm 295 295 295 WIDTH mm 1270 1570 1870 DEPTH mm 410 410 410 WEIGHT kg 23 28 33 FEATURES ACCESSORIES CWM CWM L Top air...

Страница 3: ...ostat they also need a means of signalling heating or cooling status of the flow eg a pipe thermostat kit shown on page 23 4 pipe systems require two valves but no pipe thermostat is needed VALVE POSI...

Страница 4: ...39 1 44 3 47 2 46 8 41 6 40 8 51 33 27 MED 43 8 49 1 51 3 51 3 46 7 39 5 55 37 32 MAX 45 5 50 5 53 7 52 9 48 7 40 8 57 39 34 105 MIN 34 1 38 44 42 3 41 38 48 30 24 MED 42 7 45 8 48 9 49 1 44 2 38 1 5...

Страница 5: ...1 92 2 15 2 15 3 04 3 04 27 19 7 15 1 73 1 73 1 84 1 84 2 25 2 25 27 19 9 13 2 48 2 17 2 66 2 36 3 3 3 16 27 19 9 15 1 67 1 67 1 78 1 78 2 58 2 58 27 19 9 17 1 49 1 49 1 59 1 59 1 93 1 93 29 19 5 9 3...

Страница 6: ...3 2 77 2 77 4 34 3 81 5 01 4 43 27 19 7 15 2 49 2 49 2 83 2 83 3 08 3 08 27 19 9 13 4 2 3 33 5 01 4 07 5 59 4 66 27 19 9 15 2 41 2 41 2 76 2 76 3 64 3 64 27 19 9 17 2 14 2 14 2 43 2 43 2 63 2 63 29 19...

Страница 7: ...3 4 71 3 64 6 02 4 71 7 69 6 26 27 19 7 15 2 82 2 82 3 33 3 33 4 89 4 89 27 19 9 13 4 96 3 74 6 17 4 77 7 75 6 28 27 19 9 15 2 72 2 72 4 17 3 99 5 5 5 41 27 19 9 17 2 43 2 43 2 85 2 85 3 39 3 39 29 19...

Страница 8: ...8 INSTALLATION HANGING RAIL FIXING THE HANGING RAIL HANGING THE UNIT CHASSIS...

Страница 9: ...rique Ohne Elektroheizung H Electric Heaters Batterie Electrique Mit Elektroheizung H 1 3 kW CWM 55 1 8 kW CWM 75 2 3 kW CWM 105 230V FUSE RATING TAILLE DES DISJONCTEURS EMPFOHLENE SICHERUNG EN60269 E...

Страница 10: ...z vous effectu une recherche de fuites 5 La taille du disjoncteur est elle correcte 10 6 Les c blages d interconnexions sont ills corrects 10 7 Le syst me r pond t il correctement la t l commande 8 L...

Страница 11: ...rly To remove filters Clean the filters by washing in tepid water vacuuming or by tapping gently outside the building To replace filters THE UNIT SHOULD ALWAYS BE USED WITH A FILTER FAILURE TO DO SO W...

Страница 12: ...12...

Страница 13: ...arked area and push off the cover Insert the batteries ensuring correct polarity The display will blank and reset Replace the cover by sliding into position Operating instructions are on page 16 For c...

Страница 14: ...14 CWM WIRING DIAGRAM CWM L WIRING DIAGRAM OPTIONAL ACCESSORIES...

Страница 15: ...ating is available unit heats when required but cannot cool AUTO COOL HEAT Unit cools or heats when required if heating is available 3 Setting the Fan Speeds Repeated pressing of the fan speed selecti...

Страница 16: ...Amber Red Red Green OFF OFF OFF OFF No power manual OFF timed OFF condensate high level fault in condensate control OFF ON OFF ON Cooling mode selected BLINKS ON OFF ON AUTO predominantly cooling ON O...

Страница 17: ...o 6 screws 55600401 402 403 4 2 Cable ties 8 1 Terminal 55600411 412 413 9 1 Jumper bar 55600411 412 413 This kit is for use on all CWM and CWM L wall mounted units it cannot be fitted to CWM L units...

Страница 18: ...e relay to the back panel using the 2x No 6 screws 7 c Route the harness from the fuse along the back panel using the cable clamps ensuring the harness is above the cabinet fixing brackets 3 d If ther...

Страница 19: ...has dropped below a pre set level It is easier to fit this kit before installing the unit IF THE UNIT HAS BEEN INSTALLED ISOLATE THE SYSTEM BEFORE FITTING THE KIT 1 CABINET REMOVAL 2 FITTING THE KIT...

Страница 20: ...dropped below the level of this probe e Replace the cabinet Note Whenever the electrical supply to a unit fitted with a condensate pump and controls is interrupted a delay of up to 1 minute will occu...

Страница 21: ...IMED CON CONSTANT ON ADV ADVANCE Max Switched Current 3 A fan load The timer will accommodate 0 75mm2 to 2 5mm2 wires Three core cable is required between the timer and the air conditioning unit The t...

Страница 22: ...tat 2 1 Sachet of heat sink paste 3 1 Spring band 4 1 Plastic banding 5 2 Plastic clips ISOLATE THE SYSTEM ELECTRICALLY PRIOR TO INSTALLATION OF THIS KIT 1 The pipe thermostat should be secured to the...

Страница 23: ...FO 2 port valve CW 97300425 FFO 2 port valve LPHW 1 The pipes supplied are to assist installer connection to the appropriate valve 2 Use the supplied nuts and olives as Fig 1 The sleeve is only for in...

Страница 24: ...ve Replace if faulty B Inadequate cooling or heating Dirty coil fins filter Clean if blocked Fan motor not running at required speed As in section A Faulty thermostat or incorrectly set Replace if fau...

Страница 25: ...er coil 36 Terminal mounting bracket 7 Drain tray clip 22 Heater elements 37 Electrics panel 8 CW coil rear 23 Heater coil retaining clip 38 IR PCB mounting bracket 9 Fan 24 Heater cutout bracket 39 F...

Страница 26: ...L H 5 Vertical air deflection vane 9 Horizontal air deflector vane lower 2 Cover centre 6 Grille R H 10 Horizontal air deflector vane upper 3 Cover R H 7 Grille centre 11 Connecting rod 4 Filter 8 Gri...

Отзывы: