6-30
Error Messages
6-00058-05 Rev A
94 xx yy
Communication was established between the Library and the tape drive
but the Library cannot determine the status of a particular Tape drive.
Action 1
Use the modifier
xx yy
to locate the failing tape drive:
•
xx
= rack number (1 to 16)
•
yy
= drive location (1 to 48)
Where 1 is the bottom right drive location (viewing from the back of the
module) and 48 being the top left drive location. Drives are counted from
right to left and bottom to top. Refer to
Service Action Codes
on page 6-11 for
more information on SAC modifiers.
Action 2
Do the following to power cycle the drive:
1. Vary Off the drive (
Main Menu
Utils
Drives
Status Change
Vary
Off
).
2. Reseat the drive. Wait for the following green LED blink pattern: Blink,
blink, blink, pause.
3. Vary on the drive (
Main Menu
Utils
Drives
Status Change
Vary
On
).
4. Retry the operation that failed.
Action 3
If the problem is not corrected or persists, contact GCH. For GCH contact
information, refer to
Getting More Information or Help
on page 1-8.
Table 6-2
Service Action Codes (Continued)
Reported
SAC
Perform these actions
Содержание Scalar 10K
Страница 10: ...1 x Contents 6 00058 05 Rev A...
Страница 22: ...2 xxii Figures 6 00058 05 Rev A...
Страница 24: ...3 xxiv Tables 6 00058 05 Rev A...
Страница 26: ...1 2 About This Guide 6 00058 05 Rev A...
Страница 34: ...1 10 About This Guide 6 00058 05 Rev A...
Страница 36: ...2 2 System Description 6 00058 05 Rev A...
Страница 49: ...Internal Components 2 15 September 2007 Figure 2 7 I E Station Magazines...
Страница 51: ...Connectivity 2 17 September 2007 Figure 2 8 Indirect Fibre Channel Attachment...
Страница 58: ...3 2 System Description 6 00058 05 Rev A...
Страница 252: ...4 174 Menus and Commands 6 00058 05 Rev A...
Страница 254: ...5 2 Processing Media 6 00058 05 Rev A...
Страница 276: ...6 2 Error Messages 6 00058 05 Rev A...
Страница 318: ...6 44 Error Messages 6 00058 05 Rev A...
Страница 324: ...in 6 Index 6 00058 05 Rev A...