35
Input
terminal
function
NO.
Function name
Description
4
Jog run mode
ON: Jog run
OFF: Jog run canceled
5
Acceleration/deceleration
2 pattern selection
ON: Acceleration/deceleration 2
OFF: Acceleration/deceleration 1
6
Preset-speed command 1
7
Preset-speed command 2
8
Preset-speed command 3
9
Preset-speed command 4
See f716 ~f730
10
Reset command
ON: Acceptance of reset command
ON → OFF: Trip reset
11
Trip stop command from
external input device
OFF: No Trip
ON: e-43 Trip stop according to the stop
mode set by f403
13
DC braking command
OFF: No DC braking command
ON: DC braking started. DC braking current
level and DC braking time is set by f507
and f508 respectively.
14
PID control disabling
OFF: PID control enabled.
ON: PID control disabled.
The input terminal function of PID control
disabling is used for switching between PID
control and open-loop control. Clearance of
PID integral value function can also be
used.
15
Permission of parameter
editing
ON: Parameter editing permitted
OFF: Parameter editing prohibited (If f602
= 1)
16
Combination of standby
and reset commands
OFF: Inverter motor ouput disable, motor
stop free
ON: Inverter is ready for running
From ON to OFF inverter will be reset
(Please confirm the fault has been cleared)