33
NO.
Parameter Name
Setting Range
Default
f218
point 1 output frequency
(
f1
)
0~f220
10.0
f219
point 1 output frequency voltage
(
V1
)
0~100%
20.0
f220
point 2 output frequency
(
f2
)
f218~f220
20.0
f221
point 2 output frequency voltage
(
V2
)
0~100%
40.0
f222
point 3 output frequency
(
f3
)
f220~f101
30.0
f223
point 3 output frequency voltage
(
V3
)
0~100%
60.0
Set up the V/f pattern with f218~f223 as shown in according to the load characteristic.
Note 1: The following condition must be true when setting up the V/f pattern : V1<V2<V3,
f1<f2<f3.
Note: Too high voltage output at low speed will cause a serious motor heat dissipation
problem, or stall prevention alarm, or over current trip.
Figure 2.7 Multi-point profile V/F patter (f217 =2)
2.4 Process PID parameter group
NO.
Parameter Name
Setting Range
Default
f300
AI1 terminal function selection
0~2
0
0: AI1 - analog input
1: AI1 - contact input (Sink mode)
2: AI1 - contact input (Source mode)
V2
V1
10
00
%V
b
f1
f2
f
b
f3
V3
V0
V0
=
f
202