The choice of inverter depends on the country of the installation (see table 1): 

• In countries where functional grounding is not required: inverters with or without transfor-

mers can be used. 

•  In countries where functional grounding is required, or when a system is installed within 500 

meters from the coastline, or when the module is integrated into the roof (i.e. BIPV): inverters 
with galvanically isolated transformers must be used.

Irrespective of the installation country, please follow the instructions for the use of inverters 
with transformators as provided in the following section „Functional grounding.“ Also, refer to 
the specification and instructions as provided by the inverter manufacturer.

Install a functional grounding to the DC side of the solar array, when: 

• you install in a country where functional grounding is required according to table 1. 
• you install within 500 m from the coastline.

INVERTER

FUNCTIONAL GROUNDING

INSTALLATION AND OPERATION MANUAL FOR CIGS SOLAR MODULES Q-CELLS SE - EUROPE

5.5 GROUNDING

INSTALLATION SITE

GROUNDING RECOMMENDATION Q.SMART, Q.SMART UF, Q.SMART UF L

COUNTRIES WITHOUT GROUN-
DING REQUIREMENTS   

(Belarus, Belgium, Denmark, 
Croatia, Czech Republic, Germa-
ny, Estonia, Finland, France, 
Great Britain, Hungary, Iceland, 
Latvia, Lithuania, Luxembourg, 
Moldova, The Netherlands, Nor-
way, Austria, Poland, Romania, 
Sweden, Slovakia, Slovenia, 
Switzerland, Ukraine)

• No grounding required. Inverters with or without transformators can be used.
• Exception „BIPV installations“: The grounding recommendations for „Countries 

with Grounding Requirements“ apply.

•  Exception „installation within 500 m of coastline“: The grounding recommen-

dations for „Countries with Grounding Requirements“ apply.

COUNTRIES WITH GROUNDING 
REQUIREMENTS   

(Albania, Andorra, Bosnia and 
Herzegovina, Bulgaria, Greece, 
Italy, Kazakhstan, Malta, Mace-
donia, Monaco, Montenegro, 
Portugal, Russia, San Marino, 
Serbia, Spain, Turkey, Vatican 
City, overseas countries and 
territories as well as outermost 
regions of the EU)

• Functional grounding over a resistor (min. 35k

) to limit ground fault current to 

30 mA (e.g.:  Fronius IG Plus with resistive grounding kit, Danfoss Unilynx with 
grounding kit).

•  Disconnection of the PV system from the inverter when ground fault currents 

exceed 50 mA for a length of time of 0.4 sec. (e.g.: Bender RCMA420, DOLD IP 
5883).

•  Use of inverter with flying inductor topologies without negative potentials at the 

generator poles (e.g.: Sunways AT).

•  Use of inverter with quiet-rail topologies whereby the string potential is ensured 

not to be negative (e.g.: Voltwerk VS with 6 modules per string).

• Framed Q.SMART modules

 

only

: Functional grounding with grounding kit of in-

verter manufacturer possible (hard grounding)

SPECIAL CASE:  

THE PV SYSTEM IS FENCED OFF 

(electrical operating room)

• Countries where functional grounding is not required: inverters with or without 

transformers can be used. 

• Countries where functional grounding is required: Functional grounding is requi-

red. The grounding requirements of the row “Countries with grounding require-
ments” apply. In this special case, hard grounding is permitted for all module 
types.

TABLE 1 : 

Grounding and inverter recommendations based on country of installation and Q.SMART series module type

Содержание Q.SMART Series

Страница 1: ...Q SMART Installation and operation manual for Q SMART Q SMART UF Q SMART UF L Generation G1 3 CIGS SOLAR MODULES Valid for Europe...

Страница 2: ...CYCLING PAGE 16 9 CONTACT PAGE 17 10 APPENDIX APPLICATION NOTE GROUNDING PAGE 18 Technical parameters and design are subject to change The data sheets and customer information valid at the point in ti...

Страница 3: ...nstructions please first contact your system supplier You can find more information at our website www q cells com Q CELLS CIGS solar modules allow you to directly transform the unlimited energy provi...

Страница 4: ...erating Manual by Q Cells for further information on ap proved installation and use of this product Warning ElEctrical Hazard Do not disconnect under load Q SMart UF l 100 PrOdUct Field wiring Copper...

Страница 5: ...yourself to the national regulations for work safety and accident prevention Wear suitable protective clothing e g safety shoes protective gloves in order to prevent injuries Protect the modules again...

Страница 6: ...s Solar modules are not explosion proof operating equipment The modules are not suitable for mobile usage or for indoor installations Optimal solar irradiation results in a maximum energy yield For th...

Страница 7: ...ools mounting materials or solar modules can fall and injure people Block off the danger area on the ground before begin ning the assembly work Warn people near the danger area or in the building Keep...

Страница 8: ...ules may be installed in landscape or portrait format Install the module in such a way that the junction box is positioned in the upper area of the module and the wires hang downwards Ensure that the...

Страница 9: ...ted as a coordinated unit To ensure a long term stability of the solar modules Install the module according to the mounting variants and the defined clamp areas Please refer to the Q CELLS clamp list...

Страница 10: ...s edge to the first active cell is 18 5 mm Figure 3 Ensure that clamps overlap the glass edge Figure 3 10 mm to 15 mm on the top side of the module 12 16 mm on the module back side These specification...

Страница 11: ...mm Clamp height corresponding to 36 mm frame height Figure 4 Clamp depth 7 12 mm Figure 4 Clamp area clamp depth x clamp width 600 mm Clamps that comply to the local statics requirements Clamps that...

Страница 12: ...to account all working conditions and relevant technical regu lations and standards In this way you ensure that the maximum system voltage including the necessary safety supplements are not exceeded A...

Страница 13: ...commendations for Countries with Grounding Requirements apply Exception installation within 500 m of coastline The grounding recommen dations for Countries with Grounding Requirements apply COUNTRIES...

Страница 14: ...mum voltage system or b ground fault currents 50 mA don t exceed a length of time of 0 4 s are detectable and preventable with certainty A simple ground fault safety device must not be used Specificat...

Страница 15: ...lar cables and insulated compatible connectors Q SMART modules uses MC4 connectors Only use additional components which are compatible with the modules and its electrical specifications Ensure that al...

Страница 16: ...water from the module Do not use abrasive detergents or surface active agents e g soap Do not scratch dirt off This can damage the surface of the module Modules must not be covered by snow or ice for...

Страница 17: ...allee 17 21 06766 Bitterfeld Wolfen Germany TEL 49 0 3494 66 99 0 FAX 49 0 3494 66 99 199 EMAIL service q cells com WEB www q cells com Subject to change Q Cells SE Installation and operation manual C...

Отзывы: