Installation Guide / ComT 2.0: 5°, 10° and 15°
22
Code-Compliant Planning and Installation Guide V1.0 - Complying with AS/NZS1170.2-2011 AMDT 2-2016
August 2021
31 August 2021
Clenergy Australia
1/10 Duerdin Street
Clayton, VIC 3168
CERTIFICATION LETTER
Clenergy PV ez‐Rack Commercial Tilt 5 degrees Certification – TC2, 2.5, 3 – Wind Region A, B, C, D.
Project No.:
CL‐619‐S‐REV1. Internal REF: 00489.
MW Engineering Melbourne, being Structural Engineers within the meaning of Australian
regulations, have calculated the maximum spacings for the PV ez‐Rack rail system for the following
conditions:
‐
Wind Loads to AS 1170.2‐2011 AMDT 4‐2016
o
Wind Terrain Category 2, 2.5 and 3
o
Wind average recurrence of 500 years
o
Wind Region A, B, C, D
‐
Solar panel length up to 2.4 m
Attached are the tables showing the spacings according to Wind Region, roof pitch, and building
height.
The values shown on these tables will be valid unless an amendment is issued on any of the
following codes:
‐
AS/NZS 1170.0‐ 2002 AMDT 4‐2016
General Principles
‐
AS/NZS 1170.1‐ 2002 AMDT 4‐2016
Imposed Loadings
‐
AS/NZS 1170.2‐ 2011 AMDT 4‐2016
Wind Loadings
‐
AS/NZS 1664.1‐ 1997 AMDT 1:1999
Aluminium Code
Should you have any queries, do not hesitate to contact us.
Best Regards,
Alberto Escobar
Civil/Structural Engineer
BEng MIEAust NER
PE003615
RPEQ 18759
- Certification -
Certification