PUREGAS, LLC
P4200W2 Series Air Dryer User’s Guide
Page 10 of 113
P012308 - Rev. E
5.4 Technical Specifications
P4200W2
P4200W2LP
P4202W2
P4202W2
LP
P4202W2H
Output
Capacity
Normal: 74 SCMD Maximum: 119 SCMD
Normal: 90 SCMD
Max: 119 SCMD
Power
Requirements
110 - 125 VAC, 1 Phase,
50 / 60 Hz
220 - 230 VAC, 1 Phase,
50 / 60 Hz
220-230 VAC, 1 Phase,
50Hz
Running Amps
8.6 Amps
(15 Amp service
recommended)
3.9 Amps
(15 Amp service
recommended)
4.2 Amps
(15 Amp service
recommended)
Outlet Pressure
Range
35 - 138
KPa
2 – 69
KPa
35 - 138
KPa
2 – 69
KPa
35 – 138
KPa
Outlet Air
Humidity
Less than 2% RH
Compressor
2-cylinder, 3/4 HP, oil-less type compressor
Drying Method
Heatless Desiccant
Operating
Temperature
Range
5
°
to 30
°
C (optimal)
Noise Level:
63 dBA @ 1m
Heat
Dissipation
3,521 BTU / hr
2,924 BTU / hr
Alarms
Standard alarms – complete readings of all critical measurement points, individual
alarm indication display
Monitoring
Web Browser and SNMP compatible communications via Network IP
Outlet
Connections
1/2” NPT Female
Dimensions
53cm D x 64cm W x 124cm H
Net / Shipping
Weight
100 kgs / 126 kgs