![Pulsar Measurement Greyline AVFM 6.1 Скачать руководство пользователя страница 48](http://html1.mh-extra.com/html/pulsar-measurement/greyline-avfm-6-1/greyline-avfm-6-1_instruction-manual_1625414048.webp)
AVFM 6.1 INSTRUCTION MANUAL
48
MODBUS® MEMORY MAP
Register
Address
Description
Register
Type
Data
Range
Over
Range
Read/
Write
Comments
1
Reset Volume
Total
Coil
NA
NA
Read/
Write
Turn coil ON (1) to reset total on AVFM 6.1.
Turn coil to OFF (0) once reset is complete.
Register
Address
Description
Register
Type
Data
Range
Over
Range
Read/
Write
Comments
10001
Pulse Output 1
Status
Discreet
Input
NA
NA
Read
(0) indicates pulse output is OFF or inactive.
(1) indicates pulse output is ON or active.
10002
Pulse Output 2
Status
Discreet
Input
NA
NA
Read
(0) indicates pulse output is OFF or inactive.
(1) indicates pulse output is ON or active.
Register
Address
Description
Register Type Format Type
Comments
30001
Flow Velocity - ft/s
Input Register
Floating Point Register (1 of 2)
30002
Flow Velocity - ft/s
Input Register
Floating Point Register (2 of 2)
30003
Flow Velocity - m/s
Input Register
Floating Point Register (1 of 2)
30004
Flow Velocity - m/s
Input Register
Floating Point Register (2 of 2)
30101
Flow Rate - GPM
(USG/min)
Input Register
Floating Point Register (1 of 2)
30102
Flow Rate - GPM
(USG/min)
Input Register
Floating Point Register (2 of 2)
30103
Flow Rate - L/sec
Input Register
Floating Point Register (1 of 2)
30104
Flow Rate - L/ssec
Input Register
Floating Point Register (2 of 2)
30105
Flow Rate - ft
3
/min
Input Register
Floating Point Register (1 of 2)
30106
Flow Rate - ft
3
/min
Input Register
Floating Point Register (2 of 2)
30107
Flow Rate - m
3
/hr
Input Register
Floating Point Register (1 of 2)
30108
Flow Rate - m
3
/hr
Input Register
Floating Point Register (2 of 2)
30109
Flow Rate - USG/sec
Input Register
Floating Point Register (1 of 2)
30110
Flow Rate - USG/sec
Input Register
Floating Point Register (2 of 2)
30111
Flow Rate - USG/hr
Input Register
Floating Point Register (1 of 2)
30112
Flow Rate - USG/hr
Input Register
Floating Point Register (2 of 2)
30113
Flow Rate - USG/day
Input Register
Floating Point Register (1 of 2)