PULSAR MEASUREMENT
21
DATA LOGGING
Press
or
to position curser at Data Logging, and
to enter. Use
or
to position cursor before each menu item and
to enter. When settings
are completed press
to store and
again to return to the Main Menu.
Log Site ID
Enter a number from 00 to 99. The site ID will become
part of the downloaded file name to help distinguish
downloads from different instruments. Press
to
store the setting.
Mode
Choose between LVT, Flow, Velocity, and Level mode.
Default is LVT. LVT logs flow rate, level, velocity, and
temperature simultaneously. Flow, Velocity, and Level
modes only log the parameter described. We suggest
using LVT since it is useful to see the behavior of level
and velocity independently in order to understand
meter performance. The Mode cannot be changed
when the meter is Logging.
File Format
Choose .LG2 to download data in .lg2 format for
viewing on Greyline Logger software. Choose .CSV to
download data in .csv format for import directly to
Excel. This menu option can be changed at any time
without adversely affecting existing data.
Date
Press
, and
or
to scroll and select Month, Day
and Year. Press
to store the setting.
Time
Press
, and
or
to select the current time in
Hours, Minutes and Seconds. Press
to store the
setting.
Interval
Press
or
to select the logging interval. Press
to
store the setting. Pulsar Measurement recommends
choosing an interval which will give you as much
resolution as required and no more. Choosing too
often of an interval for what is required will result in
larger data files, which may take a long time to
download to USB. Reference page 15 for specific
download times. In critical installations, data should
be downloaded often.
Data Log
Stop, Start or Delete the log file. Press
or
to
select Delete and
to delete the log file. Press
or
to select Start and
to start the logger.
--Data Logging-------
Log Site ID
0
Mode
Flow
File Format
.LG2
Date
May 18/2018
Time
11:27:40
Interval
10sec
60min
30min
15min
10min
5min
2min
1min
30sec
Data Log
Stop
Start
Delete