![Pulsar Measurement Greyline AVFM 6.1 Скачать руководство пользователя страница 13](http://html1.mh-extra.com/html/pulsar-measurement/greyline-avfm-6-1/greyline-avfm-6-1_instruction-manual_1625414013.webp)
PULSAR MEASUREMENT
13
CALIBRATION
Range
Max
Only shown when the level sensor used is a through-air
PZ type. Max range should be set as the distance from
the face of the PZ sensor to the zero level reference
point of the pipe/channel it is installed above. See
drawing below.
Min
Only shown when the level sensor used is a through-air
PZ type. Min range should be set as the distance from
the face of the PZ sensor to the maximum water level
of the pipe/channel it is installed above. The water in
the pipe/channel should get no closer than 8 inches for
a PZ15-LP sensor type. See drawing below.
SUNSCREEN
SENSOR
MaxRg
Range
MinRg > dead band
--Calibration-------
Range
Max
180.00 in
Min
8.00 in
Level
Max
180.00 in
Min
1.00 in
20mA
180.00 in
4mA
0.00 in
Lvl Offset
0.00 in
LOE Time
30 sec
Level Damping
Mode
FIR
Percent
10%
Window
1.00 in
Velocity
20mA
10.00 ft/s
4mA
0.00 ft/s
Signal Cutoff
10 %
Velocity Damping
Mode
FIR
Percent
10%
Window
1.00 ft/s
Flow
Min
0.00
/m
USG
20mA
USG
500.00
/m
4mA
0.00 USG /m
Cal Constant
1.000