Test current switch
The
Fehler! Verweisquelle konnte nicht gefunden werden.
has a test current switch. If it is activated a constant
current signal is passed to the output which is equal to the middle of the adjusted temperature range.
For 4 to 20 mA
10 ma and for 0 to 20 mA
10 mA
The correct cabling and adjustment of the middle temperature of the adjusted temperature range or sub
temperature range can be controlled easily and fast in this way.
The following parameters are adjustable only via interface:
Response time t95
The pyrometers response time characterizes the time span in which the measured temperature during erratic
variation has to coincide with the measuring field so the pyrometer is able to reach 95 % of the initial value of
the measured temperature. The minimal response time within this series of devices is 10 ms and is set by
the value „min“. Different response times can be adjusted in steps up to 10 s. Factory setting is 200 ms.
Sub temperature range
You can set a sub temperature range for the pyrometer. The sub temperature range can only limit the
temperature range and must has a minimum span of 50 °C between lower and upper limit. This range limits
only the scaling of the current output. The lower value refers to 0/4 mA and the upper value to 20 mA.
Address/Baud rate
The address of the device can be changed with this parameter. This is important for bus systems with
multiple users. Furthermore there is the possibility to change the baud rate. Please consider that all bus
users must use the same baud rate but different addresses.