Diagnostics and Troubleshooting
MVI56-MCM
♦
ControlLogix Platform
Modbus Communication Module
ProSoft Technology, Inc.
Page 81 of 159
July 24, 2008
During module configuration, the OK will be red and the APP and BP ACT LEDs
will be on. If the LEDs are latched in this mode for a long period of time, look at
the configuration error words in the configuration request block. The structure of
the block is shown in the following table:
Offset Description
Length
0 Reserved
1
1 9000
1
2
Module Configuration Errors
1
3
Port 1 Configuration Errors
1
4
Port 2 Configuration Errors
1
5 to 248
Spare
244
249
-2 or -3
1
The bits in each configuration word are shown in the following table. The module
configuration error word has the following definition:
Bit Description
Value
0
Read block start value is greater than the database size.
0x0001
1
Read block start value is less than zero.
0x0002
2
Read block count value is less than zero.
0x0004
3
Read block count + start is greater than the database size.
0x0008
4
Write block start value is greater than the database size.
0x0010
5
Write block start value is less than zero.
0x0020
6
Write block count value is less than zero.
0x0040
7
Write block count + start is greater than the database size.
0x0080
8
0x0100
9
0x0200
10
0x0400
11
0x0800
12
0x1000
13
0x2000
14
0x4000
15
0x8000
The port configuration error words have the following definitions:
Bit Description
Value
0
Type code is not valid. Enter a value from 0 (master) to 1
(slave).
0x0001
1
The float flag parameter is not valid.
0x0002
2
The float start parameter is not valid.
0x0004
3
The float offset parameter is not valid.
0x0008
4
Protocol parameter is not valid.
0x0010
5
Baud rate parameter is not valid.
0x0020
6
Parity parameter is not valid.
0x0040
7
Data bits parameter is not valid.
0x0080
8
Stop bits parameter is not valid.
0x0100