Register Content
Description
5003
Read Reg Count
This parameter specifies the number of registers to
be transferred from the module to the processor.
Valid entry for this parameter is 0 to 5000.
5004 Backplane
Fail
This parameter specifies the number of successive
transfer errors that must occur before the
communication ports are shut down. If the
parameter is set to zero, the communication ports
will continue to operate under all conditions. If the
value is set larger than 0 (1 to 65535),
communications will cease if the specified number
of failures occur.
5005
Error Status Pointer
This parameter specifies the register location in the
module's database where module status data will
be stored. If a value less than zero is entered, the
data will not be stored in the database. If the value
specified in the range of 0 to 4940, the data will be
placed in the user data area.
5006 to 5009
Spare
8.5.2 Port 1 Setup
Register Content
Description
5010 Enable This parameter defines if this Modbus port will be
used. If the parameter is set to 0, the port is
disabled. A value of 1 enables the port.
5011 Type
This parameter specifies if the port will emulate a
Modbus master device (0), a Modbus slave device
without pass-through (1), a Modbus slave device
with unformatted pass-through (2), a Modbus slave
device with formatted pass-through and data
swapping (3), or a Modbus slave device with
formatted pass-through and no data swapping (4).
5012 Float
Flag
This flag specifies if the floating-point data access
functionality is to be implemented. If the float flag is
set to 1, Modbus functions 3, 6, and 16 will
interpret floating-point values for registers as
specified by the two following parameters.
5013 Float
Start
This parameter defines the first register of floating-
point data. All requests with register values greater
than or equal to this value will be considered
floating-point data requests. This parameter is only
used if the Float Flag is enabled.
5014 Float
Offset
This parameter defines the start register for
floating-point data in the internal database. This
parameter is only used if the Float Flag is enabled.
5015 Protocol This parameter specifies the Modbus protocol to be
used on the port. Valid protocols are: 0 = Modbus
RTU and 1 = Modbus ASCII.
5016 Baud
Rate
This is the baud rate to be used on the port. Enter
the baud rate as a value. For example, to select
19K baud, enter 19200. Valid entries are 110, 150,
300, 600, 1200, 2400, 4800, 9600, 19200, 28800,
384 (for 38400bps), 576 (for 57600bps), and 115
(for 115,200bps).