![ProSoft Technology MVI56-MCM Скачать руководство пользователя страница 56](http://html1.mh-extra.com/html/prosoft-technology/mvi56-mcm/mvi56-mcm_user-manual_1618909056.webp)
MVI56-MCM
♦
ControlLogix Platform
Configuration as a Modbus Slave
Modbus Communication Module
Page 56 of 159
ProSoft Technology, Inc.
July 24, 2008
5.4 Slave
Configuration
Any parameters not mentioned in this section are not used when the module is
configured as a Modbus Master. Parameters in
BOLD
are required for all
applications as a slave.
Value Description
Enabled
1= enable port, 0 = disable port
Type
1= Modbus slave port
2= Modbus slave port with pass thru (not recommended, see note
in Overview (page 49)).
3 = Modbus slave port with formatted pass thru and data values
swapped
4 = Modbus slave port with formatted pass thru (no swapping).
FloatFlag
As a Slave, emulates Enron/Daniel style floats. See Float Point
Data Handling (page 57) for more information.
FloatStart
Register offset in message for floating data point. See Float Point
Data Handling (page 57) for more information.
FloatOffset
Used to locate the floating point data into the module memory.
Refer to "Floating Point Support."
Protocol
0 = Modbus RTU mode, 1 = Modbus ASCII mode
Baudrate
Sets the baud rate that the port will operate at. Valid values for this
field are 110, 150, 300, 600, 1200, 4800, 9600, 19200, 384 or 3840
(for 38,400 baud), 576 or 5760 (for 57,600 baud) and 115,1152, or
11520 (for 115,200 baud)
Parity
0 = None, 1 = Odd, 2 = Even
DataBits
8 = Modbus RTU mode, 8 or 7 = Modbus ASCII mode
StopBits
Valid values are 1 or 2
RTSOn
0 to 65536 milliseconds delay before it issues the message
RTSOff
0 to 65536 milliseconds delay after it issues the message
MinResp milliseconds
wait
before response to the master
UseCTS
If the parameter is set to 0, the CTS line will not be monitored. If
the parameter is set to 1, the CTS line will be monitored and must
be high before the module will send data. This parameter is
normally only required when half-duplex modems are used for
communication (2-wire)
SlaveID
Valid values are 1 to 247
BitInOffset
Register value to offset address 10001 of the module memory
WordInOffset
Register value to offset address 30001 of the module memory
OutOffset
Register value to offset address 0001 of the module memory.
HoldOffset
Register value to offset address 40001 of the module memory
InterCharacterDelay
0 to 65535 milliseconds time between characters to signal end of
message