3.3 Verify
Communication
3.3.1 Wireless Statistics Page
The
W
IRELESS
S
TATISTICS
page opens when you expand the
D
IAGNOSTICS
folder,
and then click the
W
IRELESS
S
TATISTICS
link on the left side of the page. Use this
page to view configuration and status information for the Wireless port on the
ILX34-AENWG.
Link Information
Field Description
Signal Strength
The colored graph indicates the signal level (page 56).
Signal to Noise
< 0 , this is a BAD condition
< 10, this is an OK condition
> 10, this is a GOOD condition
Radio Link Time
The up-link time in days:hours:minutes:seconds.
Note: This link status is checked at the Refresh rate, once
every 10 seconds by default. If the link is down for less time
than this, the up-time for the link will not get reset to 0.
Radio Parent MAC
The MAC address (hexadecimal) of the parent radio (access
point)
Data Rate
Rf rate of the last packet received by the ILX34-AENWG.
Although this field is informational, some packets, such as
802.11 management packets, will be at a rate that is lower than
the data. In such an instance, the data could be going at a rate
faster than this.