Procedures ILX34-AENWG
♦
POINT I/O Platform
Setup Guide
Wireless Point I/O Adapter
ProSoft Technology, Inc.
Page 51 of 79
July 31, 2009
Verify the Chassis Size
You must configure the chassis size for the ILX34-AENWG before you can make
any I/O connections (page 31). The default setting for the chassis size is 1 slot,
which represents the adapter by itself.
When the adapter's non-volatile chassis size does not match the actual number
of modules present on its backplane, the adapter does not make any I/O
connections and an error occurs, as shown in the
M
ODULE
P
ROPERTIES
dialog
box.
This procedure synchronizes the chassis size value from the RSLogix 5000
software into the ILX34-AENWG hardware. You must be online to perform this
procedure.
1
Verify that RSLogix 5000 software is online to the processor.
2
Double-click the
ILX34-AENWG
adapter under
I/O
C
ONFIGURATION
in the
C
ONTROLLER
O
RGANIZATION
window. This action opens the
M
ODULE
P
ROPERTIES
dialog box.
3
On the
M
ODULE
P
ROPERTIES
dialog box, click the
C
ONNECTION
tab. Notice
that the
M
ODULE
F
AULT
area of the dialog box contains information about the
error code.