3.2.9 Example 1 - Direct Connection and Rack Optimization
This example configures your ILX34-AENWG for both direct connection and rack
optimization using RSLogix 5000 software.
You can mix communication formats for different I/O modules communicating
through the same adapter.
I/O modules set up to use rack optimization communicate at the rate of the
RPI configured for the ILX34-AENWG adapter.
I/O modules configured for direct communication communicate at their own
set RPI and ignore the ILX34-AENWG adapter RPI.
Attention:
You must use series C POINT I/O modules with the ILX34-AENWG adapter. Series A
or B POINT I/O modules will not work with this adapter.
Add the Relay Output Module and Configure for Direct Connection
1
Right-click the ILX34-AENWG adapter under the I/O Configuration folder and
select
N
EW
M
ODULE
.
2
In the
S
ELECT
M
ODULE
dialog box, choose the
1734-OW2
relay output
module from the list, and click
OK
.