![ProSoft Technology inRA-x ILX34-AENWG Скачать руководство пользователя страница 31](http://html1.mh-extra.com/html/prosoft-technology/inra-x-ilx34-aenwg/inra-x-ilx34-aenwg_setup-manual_1618905031.webp)
Procedures ILX34-AENWG
♦
POINT I/O Platform
Setup Guide
Wireless Point I/O Adapter
ProSoft Technology, Inc.
Page 31 of 79
July 31, 2009
Configure Chassis Size
The ILX34-AENWG requires configuration of its chassis size before you can
make any I/O connections. The default setting for the chassis size is 1 slot, which
represents the adapter by itself, and allows for no I/O.
You must set the chassis size to a number equaling 1 slot for the adapter plus 1
slot for each I/O module present in the adapter's backplane. For example, the
adapter plus 2 I/O modules uses a chassis size of 3. The adapter stores this
chassis size setting in non-volatile storage.
When the adapter's non-volatile chassis size does not match the actual number
of modules present on its backplane, the adapter does not make any I/O
connections and an error occurs.
1
In the Module Definition area of the General tab, click the
C
HANGE
button.
This action opens the
M
ODULE
D
EFINITION
dialog box.
2
Select the Chassis Size for your project from the dropdown list, and then
Click
OK
to close the
M
ODULE
D
EFINITION
dialog box. In a later step, you will
verify the chassis size when you are online with the ILX34-AENWG.