41/61
c0
Delay
time
between
the
regulator
start-up
and
the
compressor
start-
up
3
3
3
c1
Delay
between
2
compressor
start-ups.
6
6
6
c2
Compressor
minimal
stop
delay.
1
1
1
c3
Compressor
minimal
operating
time.
0
0
0
c4
Duty
setting
delay
(0=off,
100=on
).
see
duty
setting
0
0
100
cc
Continuous
cycle
length.
0
0
0
c6
Time
out
after
a
continuous
cycle.
2
2
2
d0
Type
of
defrosting:
0=electrical
defrost,1=hot
gas,
2=resistors
with
operating
time,
3=
hot
gas
with
operating
time
0
0
0
dI
Interval
between
two
defrost
cycles
6
6
6
dt
Temperature
set
point
to
end
the
defrost
cycle
7
7
7
dP
Maximal
defrost
cycle
duration
(or
standard
operating
time
if
d0
=2
or
3)
30
30
30
d4
Launch
a
defrost
cycle
when
the
regulator
is
starting-up
(0=no,
1=yes)
1
1
1
d5
Defrost
cycle
starting-up
delay
or
using
a
digital
input
(A4
or
A5
=
4)
1
1
1
d6
Freeze
the
display
during
a
defrost
cycle
(0=no,
1=yes
)
1
1
1
dd
Draining
delay
after
a
defrost
cycle
0
3
3
d8
Alarm
temporisation
after
a
defrost
cycle,
if
A4
or
A5=5
;
maximal
compressor
stop
delay
and
temperature
alarm
1
1
1
d9
Defrost
priority
over
compressor
protections.
(0=no,
1=yes)
0
0
0
d/
Defrost
probe
reading
-
-
-
dC
Time
base
(0=hours/min,
1=min/sec
)
0
0
0
A0
Alarms
and
cooler
fans
differential.
4
4
4
AL
Low
temperature
alarm
(minimal
variation
allowed
around
the
set
point).
If
AL=0
this
alarm
is
disabled.
2
2
0
AH
High
temperature
alarm
(maximal
variation
allowed
around
the
set
point).
If
AH=0
this
alarm
is
disabled
4
4
4
Ad
Temperature
alarm
delay
30
30
30
A4
Digital
input
ID1
configuration:
A4=0
disable
input
A4=1
external
alarm
non-delayed
(contact
opened
=alarm)
A4=2
external
alarm
delayed
(contact
opened=alarm:delay
A7)
A4=3
defrost
cycle
enable/disable
(contact
opened=defrost
cycle
is
disabled)
A4=4
defrost
cycle
begin
(contact
is
closing=
immediate
defrost
cycle)
A4=5
Door
switch
(contact
opened
=
door
opened.
When
the
door
is
opening
the
compressor
and
the
cooler
fans
stop).
If
H1=0,
the
AUX
output
is
enable
(to
switch
the
light
on
for
example).
If
the
door
stays
opened
for
more
than
the
value
configured
in
d8,
the
display
blinks
and
the
controller
restarts.
A4=6
remote
start/stop
(contact
closed=
start).
If
both
of
the
digital
inputs
ID1
and
ID2
are
selected
as
door
switches,
the
controller
is
switched
on
only
if
both
of
the
contacts
are
closed.
When
you
select
a
remote
start/stop,
the
ON/OFF
key
on
the
keypad
is
disabled.
A4=7
shutter contact (contact closed = shutter down). If, for
example, r4=3.0 (selected value), the set point is increase of
3 °C. If the AUX output is used to control the lighting, when
the contact is switch off, the light is switched off, when the
contact is switched on, the light is switched on.
1
(0for
minicold)
1
(0 for
minicold)
1
(0 for
minicold)
A5
Digital
input
ID2
configuration:
see
A4
0
0
0
A6
Activate
the
cooling
digital
output
using
an
external
alarm
(0=off,
100=on).
Allowed
if
A4
or
A5
=
1
or
2.
see
“duty
setting”
and
digital
input
0
0
0
A7
Delay
when
A4
or
A5
=2
(external
alarm
delayed)
0
0