42/61
F0
=0
fans
are
not
controlled
by
the
cooler
temperature.
=1
thermostat
function.
The
difference
between
the
ambient
and
the
cooler
temperature
is
used
to
control
the
fans.
=2
thermostat
function.
Only
the
cooler
temperature
is
used
to
control
the
fans.
1
1
1
F1
Fans
start-up
set
point:
F0=1
fans
ON
if
T
cooler
<
(Tambient-F1-A0)
fans
OFF
if
T
cooler
>
(Tambient-F1)
F0=2
fans
ON
if
T
cooler
<
(F1-A0)
fans
OFF
if
T
cooler
>
F1
4
4
4
F2
Fans
stops
when
cooling
(
0=no,
1=yes
).
Enable
if
F0=0
1
1
1
F3
Fans
stops
during
a
defrost
cycle
(
0=no,
1=yes
)
Independent
of
F0
0
1
1
Fd
Delay
after
draining.
Independent
of
F0
0
0
0
H0
Serial
address
1
1
1
H1
AUX
digital
output
configuration:
0=auxiliary
output
1
=alarm with contact normally opened (NO)
2=alarm
with
contact
normally
closed
(NC)
0
0
0
H2
0=keypad
disable
;1=
keypad
enable
;2=
keypad
&IR
disable
;
3=
IR
disable.
(note
IR=Infra
Red)
1
1
1
H3
Authorisation code for programming with the remote control
0
0
0
H4
0=
buzzer
enable
1=
buzzer
disable
0
0
0
Set
point
4
2
-20