H - I - J
PROGRAMMER’S MANUAL
V8.94.11-
- 59 -
Submenu
Explanation, further submenus
Values
Default setting
Unit
9-10-4 type
This refers to the input activating the program!
level:
The program runs until the input is
active.
pulse:
The program starts on pulse, its stop
can be effectuated by the end of the
time limit, a stop given from an input, or
program disabling etc.
The time of the pulse has to be longer than the
bounce filtering time set in menu
level
pulse
level
9-10-5 filter
The time elapsing between setting the inputs and
activating the program, at activating a binary
program. Filtering is useful, if selecting the binary
program will be made manually, with switches, or
with a rotating knob giving binary code. With
setting the proper value of the filtering, any
incidental program start can be avoided. The
bounce filtering of the digital inputs has its effect
even before that.
0 - 60000
500
ms
9-10-6 end
The event to be happen after finishing the
program.
normal: Finishing the programs does not release
stop command.
stop:
Finishing the programs releases also stop.
normal
stop
normal
9-11
program 1.
Enabling the program 1, setting the program parameters level.
The lower is the number of the program, the higher is its priority.
The priority of the programs is higher than that of the sequences.
9-11-1 selection
The programs which need to be operated are to
be set from “disabled”. Selecting regulation or
control overrides the operation mode of the default
setting, but not the operation mode assigned at the
input!
disable
active
control
regulation
disable
9-11-2 operation
normal: When selected, the direction set in the
default setting remains unchanged.
inverse: When selected, the default direction will
be changed.
waiting: Its setting effects waiting mode.
normal
inverse
wait
normal
9-11-3 parameters
The parameters set not to „N” overwrite the originally valid values during the program run. The rise
and fall times, depending on the mode, set the steepness limit of the regulation or control.
9-11-3-1 frequency
Control reference signal
N
0,01 - 1000,0
N
Hz
9-11-3-2 regulation reference signal
N
0,01 - 100,00
N
%
9-11-3-3 rise time
N
0,1 - 3000,0
N
s
9-11-3-4 fall time
N
0,1 - 3000,0
N
s
9-11-3-5 PID selection
N
1 - 4
N
9-11-3-6 time limit
N
0,00 - 3276,7
N