H - I - J
PROGRAMMER’S MANUAL
V8.94.11-
- 17 -
Factory setting of the quick menu
Submenu
Explanation, further submenus
Values
Default setting
Unit
Parameter - 1 -
The time of linear acceleration, in control mode.
(the time for reaching fmax or fnom starting from 0
Hz)
0,05 - 3276,7
5,00
s
Parameter - 2 -
The time of linear deceleration, in control mode.
(the time for reaching 0 Hz starting from fmax or
fnom)
0,05 - 3276,7
5,00
s
Parameter - 3 -
The motor current permitted durably. This current
value corrected with the current limit is the
maximum, which can develop.
0,5 - type-dep.
type-dependent
A
Parameter - 4 -
fmax, the highest frequency.
Even if the frequency reference signal is set to a
higher value, the fmax value is effective!
* For V3D type equipment without controlling terminal
the default setting is 100 Hz
0,1 - 1050,0
50,0 *
Hz
Parameter - 5 -
fmin, the lowest frequency.
Even if the frequency reference signal is set to a
lower value, the fmin value is effective!
0,1 - 1000,0
1,0
Hz
Parameter - 6 -
The starting voltage to be given on the motor in
standstill after start, for providing the initial flux.
0,0 - type-dep.
type-dependent
V
Parameter - 7 -
This decides the menu accessible from the
regulator terminal. With „quick” is the quick menu
accessible only, whereas with „full” the whole
menu system.
quick
full
quick