H - I - J
PROGRAMMER’S MANUAL
V8.94.11-
- 58 -
9. Programs menu
In this menu, parameters connected with special process control services can be set.
Followings can be set here:
•
counters,
•
program activations,
•
programs,
•
program sequences
The program menu includes the counters, by which the pulses given to the input can be counted and accordingly the
comparator can be activated if necessary or the equipment can be halted with stop.
With the programs the reference signal, the rise and fall steepness and the data of the PID controller can be altered in
order to facilitate the adjustment of one or more technology steps.
The programs can be activated from the input. If the time of the program elapsed, it can come back to the original
operation or it can switch off the machinery.
Using the sequences, the programs can be stringed in groups, thus more programs can be operated one after another.
Submenu
Explanation, further submenus
Values
Default setting
Unit
9-1
counter 1.
i
If a program is selected as sequence cycle, its cycle counter will be the counter with
identical number.
9-1-1 type
The actual value of the counter corresponds to the
commands of the “up”, “down” and “write” inputs
selected to the digital or virtual inputs.
normal: The actual value can only be inspected,
intervention will not be made.
start 0: On start it takes th
e state of „value”.
stop 0: On reaching the 0 value it effects stop, but
at start it takes the state of „value”.
store: The equipment saves the value of the
counter even after switching off the
operating voltage.
normal
start 0
stop 0
store
normal
9-1-2 level
0 - 10000
0
9-2
counter 2.
The setting is the same as that of item
9-3
counter 3.
9-10
program
activation
Setting the individual activation of the programs
9-10-1 selection
disabled:
when set, the individual activation
of the programs can be disabled simultaneously,
independently of their selections.
disable
connect.
direct
by start
disable
9-10-3 error signal
At program run, the time limitation will be
effectuated on the decrease of the absolute value
of the error signal below the preset value.
N
0,01 - 100,00
N
%