FAN FILTER UNIT
TROUBLESHOOTING
Troubleshooting Tips
Low Air Velocity
1. Check pre-filter media (only with optional pre-filter); replace or clean as necessary
2. Adjust variable speed control for higher blower output.
3. Check power for proper voltage, amperage, and distribution frequency.
4. Replace HEPA/ULPA filter if the velocity remains low.
High Air Velocity
1. Adjust variable speed control for lower blower output.
Non-Laminar Flow and/or
Excessive Contamination
1. Ensure that no large obstructions are upstream of airflow pattern.
2. Determine that no other air-moving devices are operating in or around cleanroom which could disrupt
the room's airflow pattern.
3. Check air velocity and if low, conduct the 'Low Air Velocity' procedure outlined above.
4. Conduct smoke and photometer test on HEPA/ULPA filter. Seal or replace.
Motor Keeps Shutting Off
1. Check if unit is ducted.
2. If no, contact Price at [email protected].
3. If yes, check inlet pressure, if positive, re-balance until inlet pressure is zero.
LED Light Turned Red
1. Refer to 'Motor Will Not Run' procedure outlined below.
LED light Turned Yellow
1. Replace filter.
Motor Will Not Run
1. Check that motor has power at correct voltage.
2. Check that the speed controller has power.
3. Check control mode on speed controller and ensure setpoint is not 0%.
4. Check control harness between speed controller and motor
If experiencing further issues with unit, contact Price Industries Fan Filter help at:
By Email:
By Phone:
(204) 654-5613 option 5
priceindustries.com | FAN FILTER UNIT - Manual
34
priceindustries.com | FAN FILTER UNIT - Manual
FAN FILTER UNIT - Manual | priceindustries.com
Содержание FFU series
Страница 39: ...37 FAN FILTER UNITS NOTES priceindustries com FAN FILTER UNIT Manual priceindustries com FAN FILTER UNIT Manual...
Страница 40: ...38 FAN FILTER UNITS NOTES FAN FILTER UNIT Manual priceindustries com...
Страница 41: ...39 FAN FILTER UNITS NOTES priceindustries com FAN FILTER UNIT Manual...