FAN FILTER UNIT
BALANCING
If the FFU is ducted and removing the duct is not possible, follow the below instructions for balancing:
Step 1:
Turn off primary air source.
Step 2:
Install an air pressure measurement device (i.e. Pitot tube) in the duct prior to the FFU inlet.
Step 3:
Power up FFU and set speed controller to desired airflow. See
Airflow Setpoint
section to determine initial setpoint.
Step 4:
Power up the airflow control device. (Ductwork should have been previously balanced)
Step 5:
Read the inlet pressure.
Step 6:
Measure airflow using flow hood.
Step 7:
Using the table below, adjust FFU controller, or upstream airflow device as required
Repeat steps 4-6 until desired airflow and inlet pressure (0.0 ± 0.05” w.g.) is achieved..
FFU Airflow
FFU Inlet Static (measured)
Action
Above Set point
Above desired pressure
Decrease airflow on airflow control device
Above Set point
Below desired pressure
Decrease FFU control setting
Above Set point
At desired pressure
Decrease Both FFU and airflow control device
Below Set point
At desired pressure
Increase Both FFU and airflow control device
Below Set point
Below desired pressure
Increase airflow on airflow control device
Below Set point
Above desired pressure
Increase FFU control setting
22
priceindustries.com | FAN FILTER UNIT - Manual
FAN FILTER UNIT - Manual | priceindustries.com