FAN FILTER UNIT
BALANCING
Balancing Un-ducted Supply Units
Step 1:
Ensure the unit and filter is properly installed.
Step 2:
Turn on FFU and set to desired airflow. See
Airflow Setpoint
section to determine initial setpoint.
Step 3:
Measure airflow using flow hood and compare against scheduled flow. Adjust speed controller as necessary to achieve
design airflow.
UN-DUCTED SUPPLY UNITS, NEGATIVE PRESSURE PLENUM
20
priceindustries.com | FAN FILTER UNIT - Manual