FAN FILTER UNIT
INSTALLATION INSTRUCTIONS
Airflow Setpoint BFC
Step 1:
Determine if BFC will be controlled using local control, BAS analog voltage signal, or BACnet. The control mode can be
confirmed by observing the cycling status readout on the LCD.
NOTE:
The control hierarchy is BACnet > BAS > Local. The control mode is based on the highest level of control provided.
Step 2:
For Local or BACnet control, determine the setpoint from the appropriate airflow formula for your model in the tables below.
If BFC is being controlled by BAS analog voltage signal, refer to "ECMSC Airflow Setpoint" section for proper input voltage (Note
this will be 2X the VDC value shown in the tables).
Set-point (ECM%) ranges from 0% - 100%
Supply - Constant Flow – Clean Filters (Forward Curved)
Voltage
Velocity
24x24
24x36
Volt
FPM
BTR - FC
RSR - FC
BTR - FC
RSR - FC
115
45-135
ECM% = (CFM/3.35) - 44
ECM% = (CFM/2.33) - 46
ECM% = (CFM/5.03) - 44
ECM% = (CFM/4.13) - 38
240
45-135
ECM% = (CFM/3.38) - 42
ECM% = (CFM/2.33) - 46
ECM% = (CFM/5.06) - 44
ECM% = (CFM/4.06) - 39
277
45-135
ECM% = (CFM/3.31) - 43
ECM% = (CFM/2.35) - 42
ECM% = (CFM/5.08) - 43
ECM% = (CFM/4.12) - 37
Voltage
Velocity
24x48
Volt
FPM
BTR - FC
RSR - FC
115
45-135
ECM% = (CFM/6.94) - 42
ECM% = (CFM/5.42) - 42
240
45-135
ECM% = (CFM/6.91) - 42
ECM% = (CFM/5.45) - 41
277
45-135
ECM% = (CFM/6.97) - 41
ECM% = (CFM/5.37) - 41
Supply - Constant Torque – Clean Filters (Backwards Curved)
Voltage
Velocity
24x36
24x48
Volt
FPM
BTR - BC
RSR - BC
BTR - BC
RSR - BC
115
45-135
ECM% = (CFM/15.74) - 14
ECM% = (CFM/15.29) - 12
ECM% = (CFM/17.03) - 16
ECM% = (CFM/18.1) - 12
240
45-135
ECM% = (CFM/15.78) - 14
ECM% = (CFM/13.76) - 15
ECM% = (CFM/16.09) - 18
ECM% = (CFM/18.28) - 12
277
45-135
ECM% = (CFM/15.56) - 14
ECM% = (CFM/13.99) - 14
ECM% = (CFM/15.68) - 19
ECM% = (CFM/17.92) - 12
Supply - Constant Torque – Clean Filters (Forward Curved)
Voltage
Velocity
24x24
24x36
Volt
FPM
BTR/FC
RSR/FC
BTR/FC
RSR/FC
115
45-90
ECM% = (CFM/10.87) - 13
ECM% = (CFM/10.23) - 11
ECM% = (CFM/10.93) - 15
ECM% = (CFM/10.73) - 15
90-135
ECM% = (CFM/7.26) - 26
ECM% = (CFM/7.72) - 18
ECM% = (CFM/6.78) - 41
ECM% = (CFM/8.12) - 25
240
45-90
ECM% = (CFM/10.82) - 13
ECM% = (CFM/11.28) - 8
ECM% = (CFM/11.3) - 13
ECM% = (CFM/11.58) - 12
90-135
ECM% = (CFM/7.27) - 26
ECM% = (CFM/7.84) - 17
ECM% = (CFM/6.92) - 39
ECM% = (CFM/8.75) - 22
277
45-90
ECM% = (CFM/9.93) - 15
ECM% = (CFM/10.32) - 10
ECM% = (CFM/11.02) - 16
ECM% = (CFM/11.12) - 14
90-135
ECM% = (CFM/7.26) - 26
ECM% = (CFM/7.71) - 18
ECM% = (CFM/7.74) - 33
ECM% = (CFM/7.92) - 26
Voltage
Velocity
24x48
Volt
FPM
BTR/FC
RSR/FC
115
45-90
ECM% = (CFM/11.84) - 17
ECM% = (CFM/12.86) - 13
90-135
ECM% = (CFM/7.43) - 48
ECM% = (CFM/7.82) - 37
240
45-90
ECM% = (CFM/11.78) - 17
ECM% = (CFM/12.72) - 13
90-135
ECM% = (CFM/7.42) - 48
ECM% = (CFM/7.86) - 36
277
45-90
ECM% = (CFM/11.74) - 17
ECM% = (CFM/12.79) - 12
90-135
ECM% = (CFM/7.33) - 49
ECM% = (CFM/7.67) - 38
10
priceindustries.com | FAN FILTER UNIT - Manual
FAN FILTER UNIT - Manual | priceindustries.com